Assessment Year 2024
Principal Product Metal Cans
NAICS 332431: Metal Can Manufacturing
SIC 3411: Metal Cans
Sales Range $50
M
to 100
M
# of Employees 65
Plant Area 218,000
ft2
Annual Production 450,000,000
pieces
Production Hrs. Annual 6,624
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,084,379 9,445,657
kWh
Electricity Demand $189,262 27,758
kW-mo/yr
Electricity Fees $87,514 -
Natural Gas $512,201 36,036
MMBtu
TOTAL YEARLY COSTS $1,873,356
RECOMMENDED SAVINGS* $73,636 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $6,659 - $7,299
58,821
kWh
- $(-640.0) -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,433 $730 $2,433
19,608
kWh
- - -
03 2.7142: Utilize higher efficiency lamps and/or ballasts $12,097 $12,467 $11,691
94,207
kWh
$1,164
-
kW-mo/yr
$(-1,197.0) $439
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $10,663 $34,431 $10,663
85,919
kWh
- - -
05 2.2425: Use flue gases to heat process or service water $28,508 $135,731 $28,508
229,720
kWh
- - -
06 2.7233: Use properly designed and sized hvac equipment $13,276 $95,533 $13,276
106,980
kWh
- - -
TOTAL RECOMMENDED $73,636 $278,892 $73,870
595,255
kWh
$1,164
-
kW-mo/yr
$(-1,837.0) $439
TOTAL IMPLEMENTED - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Personnel Changes Savings Administrative Changes Savings