Assessment Year | 2024 |
---|---|
Principal Product | Wine |
NAICS | 312130: Wineries |
SIC | 2084: Wines, Brandy, and Brandy Spirits |
Sales Range | $5 M to 10M |
# of Employees | 73 |
Plant Area |
234,000
ft2
|
Annual Production | 2,200,000
units
|
Production Hrs. Annual | 3,744
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | ||
---|---|---|---|---|---|
Electricity Usage | $291,218 | 1,242,294 |
kWh
|
$0.23 | |
Electricity Demand | $86,024 | 4,825 |
kW-mo/yr
|
$17.83 | |
Natural Gas | $26,610 | 1,422 |
MMBtu
|
$18.71 | |
Waste Disposal Costs | |||||
Water Usage | $163,132 | 15,165 |
Tgal
|
$10.76 | |
TOTAL YEARLY COSTS | $566,984 | ||||
RECOMMENDED SAVINGS* | $560,353 |
See individual recommendations below
*Non-energy impacts included in savings.
|
|||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 3.4151: Minimize water usage | $26,559 | $990 | - | - |
$26,559
-
Tgal
|
- | - | |
02 | 2.7495: Install replacement doors | $18,319 | $3,440 |
$18,319
78,165
kWh
|
- | - | - | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $1,093 | $915 |
$1,093
4,662
kWh
|
- | - | - | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $41,821 | $44,432 |
$32,468
138,513
kWh
|
$2,354
-
kW-mo/yr
|
- | $4,548 | $2,451 | |
05 | 2.2511: Insulate bare equipment | $928 | $1,336 |
$928
3,960
kWh
|
- | - | - | - | |
06 | 2.2511: Insulate bare equipment | $5,096 | $15,079 |
$5,096
21,741
kWh
|
- | - | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $10,200 | $39,025 |
$10,200
43,516
kWh
|
- | - | - | - | |
08 | 3.4151: Minimize water usage | $30,298 | $117,500 |
$(-2,461.0)
(-10,500)
kWh
|
- |
$21,092
-
Tgal
|
$11,667 | - | |
09 | 2.4322: Use or replace with energy efficient substitutes | $13,015 | $65,531 |
$7,018
29,941
kWh
|
$321
-
kW-mo/yr
|
$5,676
-
Tgal
|
- | - | |
10 | 2.9114: Use solar heat to make electricty | $297,557 | $1,115,655 |
$297,557
1,269,441
kWh
|
- | - | - | - | |
11 | 4.212: Adopt in-house material generation | $115,467 | $137,973 | - | - | - | - | $115,467 | |
TOTAL RECOMMENDED | $560,353 | $1,541,876 |
$370,218
1,579,439
kWh
|
$2,675
-
kW-mo/yr
|
$53,327
-
Tgal
|
$16,215 | $117,918 | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Usage Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs