Assessment Year | 2019 |
---|---|
Principal Product | wine |
NAICS | 312130: Wineries |
SIC | 2084: Wines, Brandy, and Brandy Spirits |
Sales Range | $100 M to 500M |
# of Employees | 177 |
Plant Area |
552,017
ft2
|
Annual Production | 12,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $502,026 | 4,332,924 |
kWh
|
$0.12 |
Electricity Demand | $345,666 | 11,681 |
kW-mo/yr
|
$29.59 |
Natural Gas | $118,471 | 15,832 |
MMBtu
|
$7.48 |
TOTAL YEARLY COSTS | $966,163 | |||
RECOMMENDED SAVINGS* | $173,620 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $133,624 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $10,552 | - | - | - |
$10,552
-
MMBtu
|
- | - | |
02 | 2.2135: Repair and eliminate steam leaks | $5,167 | $1,440 |
$5,167
48,927
kWh
|
- | - | - | - | |
03 | 2.2621: Modify refrigeration system to operate at a lower pressure | $39,996 | $12,500 |
$39,996
378,754
kWh
|
- | - | - | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $15,254 | $4,129 |
$10,712
101,436
kWh
|
$4,542
-
kW-mo/yr
|
- | - | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $12,489 | $4,651 |
$8,770
83,045
kWh
|
$3,719
-
kW-mo/yr
|
- | - | - | |
06 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,888 | $3,120 |
$4,191
39,685
kWh
|
$1,697
-
kW-mo/yr
|
- | - | - | |
07 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $292 | $163 |
$203
1,921
kWh
|
$89
-
kW-mo/yr
|
- | - | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $36,088 | $25,965 |
$33,067
191,549
kWh
|
$3,021
-
kW-mo/yr
|
- | - | - | |
09 | 2.7224: Reduce space conditioning during non-working hours | $2,925 | $3,138 |
$2,925
27,700
kWh
|
- | - | - | - | |
10 | 2.6218: Turn off equipment when not in use | $1,765 | $2,729 |
$1,180
11,172
kWh
|
$585
-
kW-mo/yr
|
- | - | - | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,111 | $11,016 |
$6,111
57,871
kWh
|
- | - | - | - | |
12 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $37,093 | $93,629 |
$24,183
229,007
kWh
|
$10,299
-
kW-mo/yr
|
- | $2,321 | $290 | |
TOTAL RECOMMENDED | $173,620 | $162,480 |
$136,505
1,171,067
kWh
|
$23,952
-
kW-mo/yr
|
$10,552
-
MMBtu
|
$2,321 | $290 | ||
TOTAL IMPLEMENTED | $133,624 | $149,980 |
$96,509
792,313
kWh
|
$23,952
-
kW-mo/yr
|
$10,552
-
MMBtu
|
$2,321 | $290 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs