Assessment Year | 2018 |
---|---|
Principal Product | Tomatoes and beans |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 700 |
Plant Area |
688,000
ft2
|
Annual Production | 800,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $2,723,525 | 34,936,802 |
kWh
|
$0.078 |
Electricity Demand | $991,762 | 65,592 |
kW-mo/yr
|
$15.12 |
Natural Gas | $4,694,097 | 977,298 |
MMBtu
|
$4.80 |
TOTAL YEARLY COSTS | $8,409,384 | |||
RECOMMENDED SAVINGS* | $317,342 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $99,894 | - |
$107,894
1,383,969
kWh
|
- | - | $(-8,000.0) | - | |
02 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $88,691 | $23,292 | - | - |
$88,691
-
MMBtu
|
- | - | |
03 | 2.7224: Reduce space conditioning during non-working hours | $7,968 | $3,477 |
$3,352
43,001
kWh
|
- |
$4,616
-
MMBtu
|
- | - | |
04 | 2.4322: Use or replace with energy efficient substitutes | $1,498 | $886 |
$1,498
19,212
kWh
|
- | - | - | - | |
05 | 2.2111: Install steam trap | $9,614 | $6,613 | - | - |
$9,614
-
MMBtu
|
- | - | |
06 | 2.1231: Establish burner maintenance schedule for boilers | $20,839 | $15,682 | - | - |
$20,839
-
MMBtu
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $54,404 | $82,459 |
$39,545
507,242
kWh
|
$12,523
-
kW-mo/yr
|
- | $2,868 | $(-532.0) | |
08 | 2.2135: Repair and eliminate steam leaks | $18,580 | $32,000 | - | - |
$18,580
-
MMBtu
|
- | - | |
09 | 2.2121: Increase amount of condensate returned | $15,854 | $35,361 |
$386
4,956
kWh
|
- |
$15,468
-
MMBtu
|
- | - | |
TOTAL RECOMMENDED | $317,342 | $199,770 |
$152,675
1,958,380
kWh
|
$12,523
-
kW-mo/yr
|
$157,808
-
MMBtu
|
$(-5,132.0) | $(-532.0) | ||
TOTAL IMPLEMENTED | - | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs