| Assessment Year | 2017 |
|---|---|
| Principal Product | Poultry Products |
| NAICS | 311615: Poultry Processing |
| SIC | 2015: Poultry Slaughtering and Processing |
| Sales Range | greater than $500 M |
| # of Employees | 1,800 |
| Plant Area |
1,500,000
ft2
|
| Annual Production | 114,000,000
units
|
| Production Hrs. Annual | 6,728
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $4,661,376 | 76,416,000 |
kWh
|
$0.061 |
| Electricity Demand | $1,510,060 | 151,008 |
kW-mo/yr
|
$10.00 |
| Natural Gas | $5,939,572 | 845,864 |
MMBtu
|
$7.02 |
| TOTAL YEARLY COSTS | $12,111,008 | |||
| RECOMMENDED SAVINGS* | $632,515 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $547,723 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,509 | $80 |
$1,232
20,187
kWh
|
$277
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $379,684 | $84,889 |
$379,684
6,224,329
kWh
|
- | - | - | - | |
| 03 | 2.6218: Turn off equipment when not in use | $10,648 | $2,311 |
$10,648
174,564
kWh
|
- | - | - | - | |
| 04 | 2.7447: Install vinyl strip / high speed / air curtain doors | $25,335 | $7,208 |
$25,335
415,328
kWh
|
- | - | - | - | |
| 05 | 2.1243: Use heat from boiler blowdown to preheat boiler feed water | $21,631 | $14,971 | - | - |
$21,631
-
MMBtu
|
- | - | |
| 06 | 2.5194: Redesign process | $46,628 | $18,660 |
$38,077
624,219
kWh
|
$8,551
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $76,288 | $138,203 |
$58,012
951,011
kWh
|
$14,379
-
kW-mo/yr
|
- | $6,409 | $(-2,512.0) | |
| 08 | 2.6218: Turn off equipment when not in use | $11,335 | $14,290 |
$11,335
185,828
kWh
|
- | - | - | - | |
| 09 | 2.2123: Insulate feedwater tank | $1,760 | $3,244 | - | - |
$1,760
-
MMBtu
|
- | - | |
| 10 | 2.2511: Insulate bare equipment | $13,080 | $26,316 | - | - |
$13,080
-
MMBtu
|
- | - | |
| 11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $44,617 | $187,946 |
$5,636
92,401
kWh
|
$1,266
-
kW-mo/yr
|
$37,715
-
MMBtu
|
- | - | |
| TOTAL RECOMMENDED | $632,515 | $498,118 |
$529,959
8,687,867
kWh
|
$24,473
-
kW-mo/yr
|
$74,186
-
MMBtu
|
$6,409 | $(-2,512.0) | ||
| TOTAL IMPLEMENTED | $547,723 | $273,404 |
$498,988
8,180,138
kWh
|
$23,207
-
kW-mo/yr
|
$21,631
-
MMBtu
|
$6,409 | $(-2,512.0) | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Administrative Changes Savings | Ancillary Material Cost Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs