Assessment Year 2016
Principal Product Wine
NAICS 312130: Wineries
SIC 2084: Wines, Brandy, and Brandy Spirits
Sales Range $10
M
to 50
M
# of Employees 113
Plant Area 180,000
ft2
Annual Production 659,000
units
Production Hrs. Annual 4,389
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $342,846 2,065,237
kWh
Natural Gas $37,918 3,811
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $287,291 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $285,763

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Primary Raw Material Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,727 - $3,407
20,521
kWh
- - $(-1,680.0) -
02 2.3137: Use power during off-peak periods $1,528 - $11
261
kWh
$1,517
-
kW-mo/yr
- - -
03 2.7224: Reduce space conditioning during non-working hours $22,945 - $7,244
43,635
kWh
- $15,701
-
MMBtu
- -
04 2.2694: Use highest temperature for chilling or cold storage $15,446 $7,297 $15,446
93,040
kWh
- - - -
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $6,250 $2,903 $6,250
35,650
kWh
- - - -
06 2.2621: Modify refrigeration system to operate at a lower pressure $57,609 $52,742 $57,609
347,016
kWh
- - - -
07 2.4322: Use or replace with energy efficient substitutes $47,178 $102,267 $47,178
284,188
kWh
- - - -
08 2.7142: Utilize higher efficiency lamps and/or ballasts $4,956 $17,949 $4,134
24,902
kWh
- - $578 $244
09 2.2511: Insulate bare equipment $6,631 $26,784 $6,631
39,945
kWh
- - - -
10 2.7135: Install occupancy sensors $3,368 $13,975 $3,368
20,288
kWh
- - - -
11 2.9114: Use solar heat to make electricty $119,653 $1,013,583 $119,653
720,756
kWh
- - - -
TOTAL RECOMMENDED $287,291 $1,237,500 $270,931
1,630,202
kWh
$1,517
-
kW-mo/yr
$15,701
-
MMBtu
$(-1,102.0) $244
TOTAL IMPLEMENTED $285,763 $1,237,500 $270,920
1,629,941
kWh
- $15,701
-
MMBtu
$(-1,102.0) $244
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Personnel Changes Savings Primary Raw Material Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs