Assessment Year | 2015 |
---|---|
Principal Product | Sway Bars |
NAICS | 332613: Spring Manufacturing |
SIC | 3493: Steel Springs, Except Wire |
Sales Range | $5 M to 10M |
# of Employees | 50 |
Plant Area |
45,000
ft2
|
Annual Production | 1,400
ton
|
Production Hrs. Annual | 2,340
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $83,696 | 633,433 |
kWh
|
$0.13 |
Electricity Demand | $52,484 | 3,346 |
kW-mo/yr
|
$15.69 |
Natural Gas | $97,007 | 14,878 |
MMBtu
|
$6.52 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $27,833 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,590 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $3,033 | - |
$3,033
22,963
kWh
|
- | - | |
02 | 2.6218: Turn off equipment when not in use | $2,285 | - |
$2,285
17,295
kWh
|
- | - | |
03 | 2.3132: Recharge batteries on during off-peak demand periods | $1,475 | $793 | - |
$1,475
-
kW-mo/yr
|
- | |
04 | 2.1121: Use insulation in furnaces to facilitate heating / cooling | $2,104 | $1,941 | - | - |
$2,104
-
MMBtu
|
|
05 | 2.2414: Use waste heat from hot flue gases to preheat | $8,415 | $12,500 | - | - |
$8,415
-
MMBtu
|
|
06 | 2.1122: Re-size charging openings or add a movable door on equipment | $601 | $1,000 | - | - |
$601
-
MMBtu
|
|
07 | 2.7135: Install occupancy sensors | $2,234 | $4,284 |
$1,388
10,509
kWh
|
$846
-
kW-mo/yr
|
- | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,459 | $24,914 |
$3,699
28,001
kWh
|
$1,760
-
kW-mo/yr
|
- | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,227 | $11,712 |
$1,384
10,474
kWh
|
$843
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $27,833 | $57,144 |
$11,789
89,242
kWh
|
$4,924
-
kW-mo/yr
|
$11,120
-
MMBtu
|
||
TOTAL IMPLEMENTED | $16,590 | $31,932 |
$10,405
78,768
kWh
|
$4,081
-
kW-mo/yr
|
$2,104
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs