Assessment Year | 2014 |
---|---|
Principal Product | Treated Wastewater |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $10 M to 50M |
# of Employees | 42 |
Plant Area |
400,000
ft2
|
Annual Production | 602,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | Arizona |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $350,547 | 4,354,643 |
kWh
|
$0.080 |
Electricity Demand | $1,188 | 417 |
kW-mo/yr
|
$2.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $7,872 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,872 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,801 | $7,043 |
$2,801
34,794
kWh
|
- | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,993 | $22,488 |
$2,914
36,194
kWh
|
$1,079 | |
03 | 2.7135: Install occupancy sensors | $1,078 | $7,359 |
$1,078
13,396
kWh
|
- | |
TOTAL RECOMMENDED | $7,872 | $36,890 |
$6,793
84,384
kWh
|
$1,079 | ||
TOTAL IMPLEMENTED | $7,872 | $36,890 |
$6,793
84,384
kWh
|
$1,079 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs