Assessment Year | 2014 |
---|---|
Principal Product | Plastic Containers |
NAICS | 326121: Unlaminated Plastics Profile Shape Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 77 |
Plant Area |
137,500
ft2
|
Annual Production | 10,000,000
lb
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $718,706 | 8,555,049 |
kWh
|
$0.084 |
Electricity Demand | $363,447 | 16,824 |
kW-mo/yr
|
$21.60 |
Natural Gas | $1,627 | 168 |
MMBtu
|
$9.71 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $227,253 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $9,614 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $10,814 | $70 |
$7,997
95,024
kWh
|
$2,817
-
kW-mo/yr
|
- | - | - | |
02 | 2.6218: Turn off equipment when not in use | $4,248 | - |
$4,248
50,570
kWh
|
- | - | - | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,366 | $4,235 |
$3,968
47,232
kWh
|
$1,398
-
kW-mo/yr
|
- | - | - | |
04 | 2.8114: Change rate schedules or other changes in utility service | $38,158 | $105,000 | - | - | $38,158 | - | - | |
05 | 2.7135: Install occupancy sensors | $2,240 | $6,743 |
$1,163
13,848
kWh
|
$1,077
-
kW-mo/yr
|
- | - | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $23,962 | $93,924 |
$23,962
285,257
kWh
|
- | - | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,341 | $15,131 |
$2,958
35,217
kWh
|
- | - | $66 | $317 | |
08 | 2.9114: Use solar heat to make electricty | $139,124 | $745,024 |
$57,649
479,812
kWh
|
$81,475
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $227,253 | $970,127 |
$101,945
1,006,960
kWh
|
$86,767
-
kW-mo/yr
|
$38,158 | $66 | $317 | ||
TOTAL IMPLEMENTED | $9,614 | $4,235 |
$8,216
97,802
kWh
|
$1,398
-
kW-mo/yr
|
- | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Administrative Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs