Assessment Year | 2014 |
---|---|
Principal Product | Packaged Produce |
NAICS | 311999: All Other Miscellaneous Food Manufacturing |
SIC | 0723: Crop Preparation Services for Market, Except Cotton Ginning |
Sales Range | $10 M to 50M |
# of Employees | 900 |
Plant Area |
190,000
ft2
|
Annual Production | 96,000,000
pieces
|
Production Hrs. Annual | 5,184
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,587,276 | 18,551,647 |
kWh
|
$0.086 |
Electricity Demand | $921,980 | 39,334 |
kW-mo/yr
|
$23.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $425,159 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $254,656 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $169,599 | $40,264 |
$19,637
229,516
kWh
|
$20,893
-
kW-mo/yr
|
$47,160
-
Tgal
|
$81,909
-
Tgal
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,241 | $840 |
$3,241
37,880
kWh
|
- | - | - | - | |
03 | 2.6218: Turn off equipment when not in use | $1,931 | - |
$1,931
22,559
kWh
|
- | - | - | - | |
04 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $21,679 | $25,614 |
$12,343
139,377
kWh
|
$9,336
-
kW-mo/yr
|
- | - | - | |
05 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $57,826 | $69,335 |
$38,323
447,913
kWh
|
$19,503
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,897 | $24,840 |
$8,856
103,505
kWh
|
$3,863
-
kW-mo/yr
|
- | - | $1,178 | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,886 | $16,744 |
$3,158
36,911
kWh
|
- | - | - | $1,728 | |
08 | 2.2511: Insulate bare equipment | $9,060 | $45,537 |
$6,308
73,727
kWh
|
$2,752
-
kW-mo/yr
|
- | - | - | |
09 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $63,378 | $31,000 | - | - | - | - | $63,378 | |
10 | 3.4131: Minimize contamination of water before treatment | $11,793 | $50,140 | - | - |
$4,309
-
Tgal
|
$7,484
-
Tgal
|
- | |
11 | 2.9114: Use solar heat to make electricty | $67,869 | $444,663 |
$49,297
599,389
kWh
|
$18,572
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $425,159 | $748,977 |
$143,094
1,690,777
kWh
|
$74,919
-
kW-mo/yr
|
$51,469
-
Tgal
|
$89,393
-
Tgal
|
$66,284 | ||
TOTAL IMPLEMENTED | $254,656 | $96,878 |
$31,980
368,893
kWh
|
$30,229
-
kW-mo/yr
|
$47,160
-
Tgal
|
$81,909
-
Tgal
|
$63,378 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Water Disposal Savings | Water Consumption Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs