Assessment Year | 2013 |
---|---|
Principal Product | magnetometers, directional sensors and electronic systems used in old an |
NAICS | 334515: Instrument Manufacturing for Measuring and Testing Electricity and Electrical Signals |
SIC | 3829: Measuring and Controlling Devices, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 105 |
Plant Area |
30,000
ft2
|
Annual Production | 0
units
|
Production Hrs. Annual | 2,250
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $101,963 | 808,713 |
kWh
|
$0.13 |
Electricity Demand | $25,880 | 2,669 |
kW-mo/yr
|
$9.70 |
Natural Gas | $16,564 | 1,777 |
MMBtu
|
$9.32 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $82,327 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $28,095 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.7224: Reduce space conditioning during non-working hours | $27,444 | - |
$19,335
153,487
kWh
|
- | - |
$8,109
-
MMBtu
|
|
02 | 2.7144: Install spectral reflectors / delamp | $651 | $420 |
$483
3,830
kWh
|
$168
-
kW-mo/yr
|
- | - | |
03 | 2.7135: Install occupancy sensors | $5,725 | $23,868 |
$4,062
32,212
kWh
|
$1,663
-
kW-mo/yr
|
- | - | |
04 | 2.8112: Combine utility meters | $1,679 | $3,085 | - | - | $1,679 | - | |
05 | 2.9114: Use solar heat to make electricty | $46,828 | $377,867 |
$43,690
337,061
kWh
|
$3,138
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $82,327 | $405,240 |
$67,570
526,590
kWh
|
$4,969
-
kW-mo/yr
|
$1,679 |
$8,109
-
MMBtu
|
||
TOTAL IMPLEMENTED | $28,095 | $420 |
$19,818
157,317
kWh
|
$168
-
kW-mo/yr
|
- |
$8,109
-
MMBtu
|
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs