Assessment Year | 2012 |
---|---|
Principal Product | Composite Wood Doors |
NAICS | 321911: Wood Window and Door Manufacturing |
SIC | 2431: Millwork |
Sales Range | $5 M to 10M |
# of Employees | 57 |
Plant Area |
303,000
ft2
|
Annual Production | 884,000
pieces
|
Production Hrs. Annual | 2,210
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $212,395 | 2,465,507 |
kWh
|
$0.086 |
Electricity Demand | $206,867 | 10,800 |
kW-mo/yr
|
$19.15 |
Natural Gas | $3,706 | 389 |
MMBtu
|
$9.53 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $66,387 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,019 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Raw Material Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $12,561 | - | - | - | - | - | $12,561 | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,459 | - |
$2,459
36,625
kWh
|
- | - | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $915 | $58 |
$413
4,792
kWh
|
$502
-
kW-mo/yr
|
- | - | - | |
04 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,237 | $239 |
$558
6,483
kWh
|
$679
-
kW-mo/yr
|
- | - | - | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $37,829 | $21,581 |
$17,076
198,238
kWh
|
$20,753
-
kW-mo/yr
|
- | - | - | |
06 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $2,063 | $2,490 | - | - | $2,063 | - | - | |
07 | 2.7135: Install occupancy sensors | $6,916 | $31,417 |
$3,126
36,286
kWh
|
$3,790
-
kW-mo/yr
|
- | - | - | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,407 | $16,180 |
$1,249
14,496
kWh
|
$1,161
-
kW-mo/yr
|
$83 | $(-86.0) | - | |
TOTAL RECOMMENDED | $66,387 | $71,965 |
$24,881
296,920
kWh
|
$26,885
-
kW-mo/yr
|
$2,146 | $(-86.0) | $12,561 | ||
TOTAL IMPLEMENTED | $13,019 | $47,836 |
$7,392
93,890
kWh
|
$5,630
-
kW-mo/yr
|
$83 | $(-86.0) | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Administrative Changes Savings | Primary Raw Material Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs