Assessment Year | 2012 |
---|---|
Principal Product | Canned Tomatoes |
NAICS | 311421: Fruit and Vegetable Canning |
SIC | 2033: Canned Fruits, Vegetables, Preserves, Jams, and Jellies |
Sales Range | $100 M to 500M |
# of Employees | 1,200 |
Plant Area |
210,000
ft2
|
Annual Production | 500,000
ton
|
Production Hrs. Annual | 2,016
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,606,552 | 15,038,592 |
kWh
|
$0.11 |
Electricity Demand | $589,821 | 28,668 |
kW-mo/yr
|
$20.57 |
Electricity Fees | $18,018 | - |
|
- |
Natural Gas | $4,248,926 | 794,998 |
MMBtu
|
$5.34 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $481,789 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $241,283 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,795 | $1,200 |
$7,795
72,991
kWh
|
- | - | - | - | |
02 | 2.2113: Repair or replace steam traps | $76,949 | $36,149 | - | - |
$76,949
-
MMBtu
|
- | - | |
03 | 2.2121: Increase amount of condensate returned | $139,563 | $85,532 | - | - |
$139,563
-
MMBtu
|
- | - | |
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $27,933 | $21,797 |
$23,995
224,672
kWh
|
$3,938
-
kW-mo/yr
|
- | - | - | |
05 | 2.2511: Insulate bare equipment | $38,824 | $39,132 | - | - |
$38,824
-
MMBtu
|
- | - | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,152 | $11,614 |
$5,560
52,064
kWh
|
$1,592
-
kW-mo/yr
|
- | - | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $52,595 | $93,960 |
$52,595
492,466
kWh
|
- | - | - | - | |
08 | 2.7135: Install occupancy sensors | $3,761 | $9,004 |
$2,251
21,073
kWh
|
$1,510
-
kW-mo/yr
|
- | - | - | |
09 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $112,997 | $524,700 |
$99,940
935,771
kWh
|
$28,644
-
kW-mo/yr
|
$(-15,587.0)
-
MMBtu
|
- | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $13,215 | $62,332 |
$7,654
71,671
kWh
|
$2,872
-
kW-mo/yr
|
- | $417 | $2,272 | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,005 | $6,397 |
$781
7,311
kWh
|
$224
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $481,789 | $891,817 |
$200,571
1,878,019
kWh
|
$38,780
-
kW-mo/yr
|
$239,749
-
MMBtu
|
$417 | $2,272 | ||
TOTAL IMPLEMENTED | $241,283 | $194,217 |
$17,700
165,735
kWh
|
$4,382
-
kW-mo/yr
|
$216,512
-
MMBtu
|
$417 | $2,272 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Primary Raw Material Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs