Assessment Year | 2011 |
---|---|
Principal Product | Chocolate |
NAICS | 311352: Confectionery Manufacturing from Purchased Chocolate |
SIC | 2026: Fluid Milk |
Sales Range | $10 M to 50M |
# of Employees | 125 |
Plant Area |
80,000
ft2
|
Annual Production | 20,000,000
units
|
Production Hrs. Annual | 3,536
hrs
|
Location (State) | Hawaii |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $225,745 | 1,313,544 |
kWh
|
$0.17 |
Electricity Demand | $33,364 | 4,008 |
kW-mo/yr
|
$8.32 |
Electricity Fees | $4,106 | - |
|
- |
LPG | $22,755 | 634 |
MMBtu
|
$35.89 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $25,132 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $23,130 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,204 | $73 |
$1,204
5,350
kWh
|
- | - | - | |
02 | 2.7132: Install timers on light switches in little used areas | $439 | $235 |
$439
2,001
kWh
|
- | - | - | |
03 | 2.3212: Optimize plant power factor | $2,952 | $3,821 | - | - | $2,952 | - | |
04 | 2.4131: Size electric motors for peak operating efficiency | $2,879 | $3,638 |
$2,879
12,787
kWh
|
- | - | - | |
05 | 2.7135: Install occupancy sensors | $7,621 | $11,002 |
$7,621
33,728
kWh
|
- | - | - | |
06 | 2.4131: Size electric motors for peak operating efficiency | $7,794 | $20,780 |
$7,794
39,582
kWh
|
- | - | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $241 | $700 |
$104
527
kWh
|
$6
-
kW-mo/yr
|
- | $131 | |
08 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,002 | $12,392 |
$2,002
7,795
kWh
|
- | - | - | |
TOTAL RECOMMENDED | $25,132 | $52,641 |
$22,043
101,770
kWh
|
$6
-
kW-mo/yr
|
$2,952 | $131 | ||
TOTAL IMPLEMENTED | $23,130 | $40,249 |
$20,041
93,975
kWh
|
$6
-
kW-mo/yr
|
$2,952 | $131 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs