Assessment Year | 2010 |
---|---|
Principal Product | Recycled Water |
NAICS | 221320: Sewage Treatment Facilities |
SIC | 4952: Sewerage Systems |
Sales Range | $1 M to 5M |
# of Employees | 45 |
Plant Area |
958,320
ft2
|
Annual Production | 4,927,000
Tgal
|
Production Hrs. Annual | 8,760
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $386,991 | 4,668,198 |
kWh
|
$0.083 |
Electricity Demand | $157,608 | 13,688 |
kW-mo/yr
|
$11.51 |
Electricity Fees | $8,229 | - |
|
- |
Natural Gas | $166,222 | 24,872 |
MMBtu
|
$6.68 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $256,791 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $31,062 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $1,075 | - | - | - |
$1,075
-
MMBtu
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $26,321 | $16,124 |
$22,282
263,696
kWh
|
$4,039
-
kW-mo/yr
|
- | - | |
03 | 2.4322: Use or replace with energy efficient substitutes | $14,943 | $11,249 |
$14,943
176,835
kWh
|
- | - | - | |
04 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $128,228 | $381,609 |
$102,021
1,207,354
kWh
|
$26,207
-
kW-mo/yr
|
- | - | |
05 | 2.4322: Use or replace with energy efficient substitutes | $25,418 | $81,160 |
$4,498
53,227
kWh
|
$5,753
-
kW-mo/yr
|
- | $15,167 | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $11,635 | $40,292 |
$9,225
109,176
kWh
|
$2,410
-
kW-mo/yr
|
- | - | |
07 | 2.7135: Install occupancy sensors | $4,484 | $17,522 |
$3,608
42,698
kWh
|
$876
-
kW-mo/yr
|
- | - | |
08 | 2.4322: Use or replace with energy efficient substitutes | $27,181 | $174,884 |
$23,009
272,290
kWh
|
$4,172
-
kW-mo/yr
|
- | - | |
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,506 | $328,173 |
$15,413
182,403
kWh
|
$2,093
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $256,791 | $1,051,013 |
$194,999
2,307,679
kWh
|
$45,550
-
kW-mo/yr
|
$1,075
-
MMBtu
|
$15,167 | ||
TOTAL IMPLEMENTED | $31,062 | $69,063 |
$27,776
328,709
kWh
|
$3,286
-
kW-mo/yr
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings |