Assessment Year | 2008 |
---|---|
Principal Product | Metal and Plastic Original Equipment Manufacturer (OEM) Labels |
NAICS | 332812: Metal Coating, Engraving (except Jewelry and Silverware), and Allied Services to Manufacturers |
SIC | 3479: Coating, Engraving, and Allied Services, Not Elsewhere Classified |
Sales Range | $5 M to 10M |
# of Employees | 65 |
Plant Area |
50,000
ft2
|
Annual Production | 1,600,000
pieces
|
Production Hrs. Annual | 2,860
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $118,697 | 880,480 |
kWh
|
$0.13 |
Electricity Demand | $17,666 | 4,530 |
kW-mo/yr
|
$3.90 |
Electricity Fees | $5,838 | - |
|
- |
Natural Gas | $11,154 | 903 |
MMBtu
|
$12.35 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $54,126 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $10,316 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $4,430 | - | - |
$4,430
-
kW-mo/yr
|
|
02 | 2.6218: Turn off equipment when not in use | $870 | $904 |
$792
5,876
kWh
|
$78
-
kW-mo/yr
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,576 | $523 |
$1,424
10,565
kWh
|
$152
-
kW-mo/yr
|
|
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,314 | $1,577 |
$1,893
14,040
kWh
|
$421
-
kW-mo/yr
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,881 | $6,200 |
$1,881
13,954
kWh
|
- | |
06 | 2.4133: Use most efficient type of electric motors | $197 | $453 |
$158
1,171
kWh
|
$39
-
kW-mo/yr
|
|
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $929 | $4,808 |
$828
6,140
kWh
|
$101
-
kW-mo/yr
|
|
08 | 2.7135: Install occupancy sensors | $955 | $6,455 |
$791
5,869
kWh
|
$164
-
kW-mo/yr
|
|
09 | 2.9114: Use solar heat to make electricty | $40,974 | $1,575,000 |
$34,059
252,642
kWh
|
$6,915
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $54,126 | $1,595,920 |
$41,826
310,257
kWh
|
$12,300
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $10,316 | $8,265 |
$5,095
37,792
kWh
|
$5,221
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs