Assessment Year 2006
Principal Product Chocolate
NAICS 311351: Chocolate and Confectionery Manufacturing from Cacao Beans
SIC 2066: Chocolate and Cocoa Products
Sales Range $100
M
to 500
M
# of Employees 200
Plant Area 600,000
ft2
Annual Production 15,000,000
lb
Production Hrs. Annual 6,240
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $1,558,332 38,653,492
kWh
Electricity Demand $944,276 77,826
kW-mo/yr
Natural Gas $4,693,182 412,864
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $54,463 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $1,017

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
01 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,017 - $1,017
39,626
kWh
- -
02 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $1,235 $117 $1,235
30,630
kWh
- -
03 2.1321: Replace fossil fuel equipment with electrical equipment $5,332 $3,710 - - $5,332
-
MMBtu
04 2.4133: Use most efficient type of electric motors $17,266 $20,534 $10,730
266,134
kWh
$6,536
-
kW-mo/yr
-
05 2.7135: Install occupancy sensors $2,860 $4,608 $1,588
39,394
kWh
$1,272
-
kW-mo/yr
-
06 2.7134: Use photocell controls $14,161 $39,154 $8,188
203,085
kWh
$5,973
-
kW-mo/yr
-
07 2.7142: Utilize higher efficiency lamps and/or ballasts $10,694 $33,264 $6,446
159,870
kWh
$4,248
-
kW-mo/yr
-
08 2.4111: Utilize energy-efficient belts and other improved mechanisms $1,898 $7,608 $1,043
25,885
kWh
$855
-
kW-mo/yr
-
TOTAL RECOMMENDED $54,463 $108,995 $30,247
764,624
kWh
$18,884
-
kW-mo/yr
$5,332
-
MMBtu
TOTAL IMPLEMENTED $1,017 - $1,017
39,626
kWh
- -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs