Assessment Year | 2005 |
---|---|
Principal Product | Metal Cabinets for Technology Companies |
NAICS | 332439: Other Metal Container Manufacturing |
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 70 |
Plant Area |
65,000
ft2
|
Annual Production | 13,440
ton
|
Production Hrs. Annual | 4,394
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $183,321 | 1,207,040 |
kWh
|
$0.15 |
Electricity Demand | $18,622 | 4,204 |
kW-mo/yr
|
$4.43 |
Natural Gas | $29,594 | 3,343 |
MMBtu
|
$8.85 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $35,265 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $3,751 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.6218: Turn off equipment when not in use | $17,326 | - |
$17,326
138,840
kWh
|
- | - | - | - | |
02 | 2.2523: Reduce infiltration to refrigerated areas; isolate hot equipment from refrigerated areas | $871 | - | - | - |
$871
-
MMBtu
|
- | - | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,751 | - |
$3,751
33,527
kWh
|
- | - | - | - | |
04 | 2.6218: Turn off equipment when not in use | $2,623 | - |
$2,623
21,018
kWh
|
- | - | - | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,248 | $499 |
$1,119
8,964
kWh
|
$129
-
kW-mo/yr
|
- | - | - | |
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $465 | $588 |
$301
2,411
kWh
|
$16
-
kW-mo/yr
|
- | $85 | $63 | |
07 | 2.7135: Install occupancy sensors | $598 | $848 |
$467
3,745
kWh
|
$131
-
kW-mo/yr
|
- | - | - | |
08 | 2.7135: Install occupancy sensors | $1,062 | $1,832 |
$952
7,625
kWh
|
$110
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,442 | $19,385 |
$3,981
31,901
kWh
|
$461
-
kW-mo/yr
|
- | - | - | |
10 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,879 | $12,894 |
$2,580
20,678
kWh
|
$299
-
kW-mo/yr
|
- | - | - | |
TOTAL RECOMMENDED | $35,265 | $36,046 |
$33,100
268,709
kWh
|
$1,146
-
kW-mo/yr
|
$871
-
MMBtu
|
$85 | $63 | ||
TOTAL IMPLEMENTED | $3,751 | - |
$3,751
33,527
kWh
|
- | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Personnel Changes Savings | Primary Raw Material Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs