Assessment Year 2004
Principal Product Wine
NAICS 312130: Wineries
SIC 2084: Wines, Brandy, and Brandy Spirits
Sales Range $10
M
to 50
M
# of Employees 58
Plant Area 28,000
ft2
Annual Production 40,000
lb
Production Hrs. Annual 3,680
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $101,373 656,252
kWh
Electricity Demand $7,344 1,635
kW-mo/yr
Natural Gas $15,719 1,398
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $13,051 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $334

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Other Gas Savings Solid Waste (non-haz) Savings
01 2.7142: Utilize higher efficiency lamps and/or ballasts $220 $204 $192
1,342
kWh
$28
-
kW-mo/yr
- -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $2,407 $1,649 $2,407
13,087
kWh
- - -
03 2.4133: Use most efficient type of electric motors $481 $380 $397
2,763
kWh
$84
-
kW-mo/yr
- -
04 2.1311: Replace electrically-operated equipment with fossil fuel equipment $842 $1,252 $1,124
7,862
kWh
$121
-
kW-mo/yr
$(-403.0)
-
MMBtu
-
05 2.7135: Install occupancy sensors $1,425 $2,689 $1,230
8,605
kWh
$195
-
kW-mo/yr
- -
06 2.2511: Insulate bare equipment $334 $1,065 $334
1,989
kWh
- - -
07 2.7142: Utilize higher efficiency lamps and/or ballasts $283 $925 $283
1,536
kWh
- - -
08 2.7145: Install skylights $954 $5,520 $954
5,186
kWh
- - -
09 3.6193: Install equipment (eg compactor) to reduce disposal costs $6,105 $10,964 - - - $6,105
-
lb
TOTAL RECOMMENDED $13,051 $24,648 $6,921
42,370
kWh
$428
-
kW-mo/yr
$(-403.0)
-
MMBtu
$6,105
-
lb
TOTAL IMPLEMENTED $334 $1,065 $334
1,989
kWh
- - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Other Gas Savings Solid Waste (non-haz) Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs