Assessment Year | 2004 |
---|---|
Principal Product | Spices |
NAICS | 311942: Spice and Extract Manufacturing |
SIC | 2099: Food Preparations, Not Elsewhere Classified |
Sales Range | $100 M to 500M |
# of Employees | 450 |
Plant Area |
500,000
ft2
|
Annual Production | 1,000,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $905,498 | 10,224,600 |
kWh
|
$0.089 |
Electricity Demand | $258,008 | 22,212 |
kW-mo/yr
|
$11.62 |
Natural Gas | $134,919 | 18,709 |
MMBtu
|
$7.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $122,551 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $67,822 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.6212: Turn off equipment during breaks, reduce operating time | $32,741 | - |
$32,741
369,532
kWh
|
- | - | |
02 | 2.6212: Turn off equipment during breaks, reduce operating time | $25,664 | - |
$25,664
289,659
kWh
|
- | - | |
03 | 2.6212: Turn off equipment during breaks, reduce operating time | $8,720 | - |
$8,720
98,423
kWh
|
- | - | |
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $7,058 | - |
$7,058
97,539
kWh
|
- | - | |
05 | 2.6212: Turn off equipment during breaks, reduce operating time | $697 | $5,675 |
$697
7,863
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $4,397 | $1,494 |
$3,542
39,979
kWh
|
$855
-
kW-mo/yr
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $6,950 | $5,385 |
$5,039
58,848
kWh
|
$1,911
-
kW-mo/yr
|
- | |
08 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $802 | $640 |
$802
9,054
kWh
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,413 | $6,109 |
$5,433
61,246
kWh
|
$1,980
-
kW-mo/yr
|
- | |
10 | 2.7134: Use photocell controls | $983 | $840 |
$653
7,368
kWh
|
$330
-
kW-mo/yr
|
- | |
11 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $4,088 | $5,198 |
$3,264
36,838
kWh
|
$824
-
kW-mo/yr
|
- | |
12 | 2.7135: Install occupancy sensors | $630 | $1,024 |
$422
4,993
kWh
|
$208
-
kW-mo/yr
|
- | |
13 | 2.4239: Eliminate or reduce compressed air usage | $5,628 | $21,299 |
$5,290
59,701
kWh
|
$338
-
kW-mo/yr
|
- | |
14 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $8,162 | $31,967 |
$8,162
92,124
kWh
|
- | - | |
15 | 2.7134: Use photocell controls | $2,513 | $12,012 |
$1,852
20,907
kWh
|
$661
-
kW-mo/yr
|
- | |
16 | 3.5218: Reuse / recycle/ sell rubber products | $6,105 | $250 | - | - |
$6,105
-
lb
|
|
TOTAL RECOMMENDED | $122,551 | $91,893 |
$109,339
1,254,074
kWh
|
$7,107
-
kW-mo/yr
|
$6,105
-
lb
|
||
TOTAL IMPLEMENTED | $67,822 | $5,675 |
$67,822
765,477
kWh
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs