| Assessment Year | 2001 |
|---|---|
| Principal Product | Metal Ingots |
| NAICS |
n/a
|
| SIC | 3349: |
| Sales Range | $10 M to 50M |
| # of Employees | 30 |
| Plant Area |
47,500
ft2
|
| Annual Production | 1,500,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $315,916 | 2,622,620 |
kWh
|
$0.12 |
| Natural Gas | $12,487 | 1,569 |
MMBtu
|
$7.96 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,828 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $14,133 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Solid Waste (non-haz) Savings |
|---|---|---|---|---|---|---|
| 01 | 2.6218: Turn off equipment when not in use | $3,760 | - |
$3,760
31,200
kWh
|
- | |
| 02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,973 | $360 |
$1,973
16,377
kWh
|
- | |
| 03 | 2.2611: Moderate cooling tower outlet temperature | $1,846 | $495 |
$1,846
15,320
kWh
|
- | |
| 04 | 2.4239: Eliminate or reduce compressed air usage | $670 | $420 |
$670
5,696
kWh
|
- | |
| 05 | 2.6218: Turn off equipment when not in use | $2,703 | $2,200 |
$2,703
23,920
kWh
|
- | |
| 06 | 2.7132: Install timers on light switches in little used areas | $4,406 | $4,080 |
$4,406
36,575
kWh
|
- | |
| 07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $7,754 | $11,785 |
$7,754
64,352
kWh
|
- | |
| 08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,572 | $6,779 |
$3,572
29,637
kWh
|
- | |
| 09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $565 | $2,735 |
$565
4,687
kWh
|
- | |
| 10 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $2,579 | $15,374 | - |
$2,579
-
lb
|
|
| TOTAL RECOMMENDED | $29,828 | $44,228 |
$27,249
227,764
kWh
|
$2,579
-
lb
|
||
| TOTAL IMPLEMENTED | $14,133 | $16,225 |
$14,133
117,304
kWh
|
- | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Solid Waste (non-haz) Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs