Assessment Year | 2001 |
---|---|
Principal Product | Corrugated containers |
NAICS |
n/a
|
SIC | 3653: |
Sales Range | $50 M to 100M |
# of Employees | 154 |
Plant Area |
350,000
ft2
|
Annual Production | 1,300,000,000
thousand feet
|
Production Hrs. Annual | 7,448
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $463,108 | 6,068,690 |
kWh
|
$0.076 |
Natural Gas | $415,337 | 82,083 |
MMBtu
|
$5.06 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $74,715 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $64,668 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.2135: Repair and eliminate steam leaks | $13,186 | $1,585 | - |
$13,186
-
MMBtu
|
- | |
02 | 2.2113: Repair or replace steam traps | $13,868 | $2,580 | - |
$13,868
-
MMBtu
|
- | |
03 | 2.7135: Install occupancy sensors | $5,381 | $1,590 | - |
$5,381
-
MMBtu
|
- | |
04 | 2.2511: Insulate bare equipment | $2,893 | $1,200 |
$2,893
41,666
kWh
|
- | - | |
05 | 2.2511: Insulate bare equipment | $13,029 | $9,546 | - |
$13,029
-
MMBtu
|
- | |
06 | 2.1224: Replace boiler | $18,515 | $22,255 | - |
$18,515
-
MMBtu
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $1,670 | $3,218 |
$1,670
24,059
kWh
|
- | - | |
08 | 2.7132: Install timers on light switches in little used areas | $1,773 | $4,250 |
$1,773
25,353
kWh
|
- | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,659 | $7,791 |
$2,659
34,852
kWh
|
- | - | |
10 | 3.5217: Reuse / recycle/ sell paper products | $1,741 | - | - | - |
$1,741
-
lb
|
|
TOTAL RECOMMENDED | $74,715 | $54,015 |
$8,995
125,930
kWh
|
$63,979
-
MMBtu
|
$1,741
-
lb
|
||
TOTAL IMPLEMENTED | $64,668 | $46,975 |
$4,329
58,911
kWh
|
$58,598
-
MMBtu
|
$1,741
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs