Assessment Year | 2000 |
---|---|
Principal Product | PC Strand Wire, Saw Wire |
NAICS |
n/a
|
SIC | 3315: Steel Wiredrawing and Steel Nails and Spikes |
Sales Range | $10 M to 50M |
# of Employees | 66 |
Plant Area |
110,000
ft2
|
Annual Production | 350,000
ton
|
Production Hrs. Annual | 6,600
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $587,068 | 14,735,453 |
kWh
|
$0.040 |
Electricity Demand | $35,274 | 34,695 |
kW-mo/yr
|
$1.02 |
Natural Gas | $43,831 | 17,971 |
MMBtu
|
$2.44 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $30,018 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $25,863 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,271 | - |
$2,271
26,269
kWh
|
- | - | - | - | |
02 | 2.6215: Shut off air conditioning in winter heating season | $1,393 | - |
$1,393
34,979
kWh
|
- | - | - | - | |
03 | 2.6218: Turn off equipment when not in use | $3,336 | $1,446 |
$3,000
75,330
kWh
|
$336
-
kW-mo/yr
|
- | - | - | |
04 | 2.6218: Turn off equipment when not in use | $360 | $370 |
$278
6,970
kWh
|
$82
-
kW-mo/yr
|
- | - | - | |
05 | 2.7135: Install occupancy sensors | $1,236 | $2,040 |
$1,181
29,650
kWh
|
$55
-
kW-mo/yr
|
- | - | - | |
06 | 2.7135: Install occupancy sensors | $851 | $2,250 |
$813
20,402
kWh
|
$38
-
kW-mo/yr
|
- | - | - | |
07 | 2.4239: Eliminate or reduce compressed air usage | $1,569 | $4,392 |
$1,499
37,616
kWh
|
$70
-
kW-mo/yr
|
- | - | - | |
08 | 2.7144: Install spectral reflectors / delamp | $7,099 | $32,250 |
$6,783
170,247
kWh
|
$316
-
kW-mo/yr
|
- | - | - | |
09 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,849 | $10,470 |
$1,739
43,645
kWh
|
$110
-
kW-mo/yr
|
- | - | - | |
10 | 3.5311: Recover and reuse waste material | $1,085 | - | - | - | - |
$1,085
-
lb
|
- | |
11 | 3.5217: Reuse / recycle/ sell paper products | $1,250 | $150 | - | - | - | - | $1,250 | |
12 | 3.3131: Use evaporation to concentrate material | $3,564 | $5,500 | - | - |
$6,564
-
gal
|
- | $(-3,000.0) | |
13 | 3.6111: Use alternative flocculent to minimize sludge volume | $4,155 | $19,400 |
$(-41.0)
(-3)
kWh
|
- | - |
$4,196
-
lb
|
- | |
TOTAL RECOMMENDED | $30,018 | $78,268 |
$18,916
445,105
kWh
|
$1,007
-
kW-mo/yr
|
$6,564
-
gal
|
$5,281
-
lb
|
$(-1,750.0) | ||
TOTAL IMPLEMENTED | $25,863 | $58,868 |
$18,957
445,108
kWh
|
$1,007
-
kW-mo/yr
|
$6,564
-
gal
|
$1,085
-
lb
|
$(-1,750.0) | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Other Liquid (haz) Savings | Solid Waste (non-haz) Savings | Administrative Changes Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs