Assessment Year | 1999 |
---|---|
Principal Product | Bleach, Chlorine |
NAICS |
n/a
|
SIC | 2812: Alkalies and Chlorine |
Sales Range | $10 M to 50M |
# of Employees | 50 |
Plant Area |
68,000
ft2
|
Annual Production | 12,000
Tgal
|
Production Hrs. Annual | 6,552
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $85,239 | 1,046,014 |
kWh
|
$0.081 |
Electricity Demand | $12,363 | 1,433 |
kW-mo/yr
|
$8.63 |
Natural Gas | $2,783 | 399 |
MMBtu
|
$6.97 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $19,604 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,474 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $615 | - |
$615
7,620
kWh
|
- | |
02 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $7,561 | $2,700 |
$6,824
84,115
kWh
|
$737
-
kW-mo/yr
|
|
03 | 2.4133: Use most efficient type of electric motors | $453 | $291 |
$413
4,982
kWh
|
$40
-
kW-mo/yr
|
|
04 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $3,921 | $3,189 |
$3,242
39,859
kWh
|
$679
-
kW-mo/yr
|
|
05 | 2.7135: Install occupancy sensors | $1,105 | $1,008 |
$1,006
12,309
kWh
|
$99
-
kW-mo/yr
|
|
06 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,910 | $8,190 |
$2,641
32,532
kWh
|
$269
-
kW-mo/yr
|
|
07 | 2.7134: Use photocell controls | $2,025 | $6,000 |
$1,769
21,688
kWh
|
$256
-
kW-mo/yr
|
|
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,014 | $4,121 |
$905
11,137
kWh
|
$109
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $19,604 | $25,499 |
$17,415
214,242
kWh
|
$2,189
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $16,474 | $18,491 |
$14,640
180,245
kWh
|
$1,834
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs