Assessment Year | 1999 |
---|---|
Principal Product | Miniature Pressure Sensors |
NAICS |
n/a
|
SIC | 3674: Semiconductors and Related Devices |
Sales Range | $10 M to 50M |
# of Employees | 170 |
Plant Area |
35,500
ft2
|
Annual Production | 15,000,000
pieces
|
Production Hrs. Annual | 8,736
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $234,682 | 3,791,618 |
kWh
|
$0.062 |
Electricity Demand | $67,203 | 5,197 |
kW-mo/yr
|
$12.93 |
Natural Gas | $16,472 | 2,696 |
MMBtu
|
$6.11 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $5,827 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $834 | $389 |
$648
10,551
kWh
|
$186
-
kW-mo/yr
|
- | |
02 | 2.4133: Use most efficient type of electric motors | $1,859 | $1,055 |
$1,444
23,447
kWh
|
$415
-
kW-mo/yr
|
- | |
03 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $1,053 | $1,408 |
$1,217
19,637
kWh
|
$349
-
kW-mo/yr
|
$(-513.0)
-
MMBtu
|
|
04 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $2,081 | $8,340 |
$5,626
90,856
kWh
|
- |
$(-3,545.0)
-
MMBtu
|
|
TOTAL RECOMMENDED | $5,827 | $11,192 |
$8,935
144,491
kWh
|
$950
-
kW-mo/yr
|
$(-4,058.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |