Assessment Year | 1999 |
---|---|
Principal Product | Printed Paper |
NAICS |
n/a
|
SIC | 2759: Commercial Printing, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 96 |
Plant Area |
66,000
ft2
|
Annual Production | 49,500,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $133,948 | 2,151,817 |
kWh
|
$0.062 |
Electricity Demand | $92,162 | 2,945 |
kW-mo/yr
|
$31.29 |
Natural Gas | $594 | 75 |
MMBtu
|
$7.92 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $123,302 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $21,608 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|---|---|
01 | 2.7135: Install occupancy sensors | $1,834 | $1,456 |
$1,040
16,706
kWh
|
$794
-
kW-mo/yr
|
- | - | - | |
02 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $18,418 | $45,400 |
$10,534
169,109
kWh
|
$7,884
-
kW-mo/yr
|
- | - | - | |
03 | 2.4231: Reduce the pressure of compressed air to the minimum required | $396 | $2,106 |
$283
4,689
kWh
|
$113
-
kW-mo/yr
|
- | - | - | |
04 | 3.5313: Increase amount of waste recovered for resale | $3,602 | - | - | - |
$3,602
-
lb
|
- | - | |
05 | 3.5316: Contract a wood pallet recycling company | $960 | $250 | - | - |
$960
-
lb
|
- | - | |
06 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $19,132 | $49,350 | - | - |
$19,132
-
lb
|
- | - | |
07 | 4.212: Adopt in-house material generation | $78,960 | $30,000 | - | - | - | $(-32,760.0) | $111,720 | |
TOTAL RECOMMENDED | $123,302 | $128,562 |
$11,857
190,504
kWh
|
$8,791
-
kW-mo/yr
|
$23,694
-
lb
|
$(-32,760.0) | $111,720 | ||
TOTAL IMPLEMENTED | $21,608 | $49,212 |
$11,857
190,504
kWh
|
$8,791
-
kW-mo/yr
|
$960
-
lb
|
- | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Personnel Changes Savings | Ancillary Material Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs