| Assessment Year | 1998 |
|---|---|
| Principal Product | Formaldehyde and Resins |
| NAICS |
n/a
|
| SIC | 2821: Plastics Materials, Synthetic Resins, and Nonvulcanizable Elastomers |
| Sales Range | $10 M to 50M |
| # of Employees | 25 |
| Plant Area |
1,437,480
ft2
|
| Annual Production | 245,000,000
lb
|
| Production Hrs. Annual | 6,240
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $275,426 | 5,390,680 |
kWh
|
$0.051 |
| Electricity Demand | $117,147 | 10,508 |
kW-mo/yr
|
$11.15 |
| Natural Gas | $146,034 | 41,602 |
MMBtu
|
$3.51 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $255,520 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $245,424 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings |
|---|---|---|---|---|---|---|---|---|---|
| 01 | 2.4322: Use or replace with energy efficient substitutes | $45,578 | $21,000 |
$32,109
628,370
kWh
|
$13,469
-
kW-mo/yr
|
- | - | - | |
| 02 | 2.4133: Use most efficient type of electric motors | $2,120 | $3,259 |
$1,481
29,015
kWh
|
$639
-
kW-mo/yr
|
- | - | - | |
| 03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,792 | $5,123 |
$2,056
40,152
kWh
|
$736
-
kW-mo/yr
|
- | - | - | |
| 04 | 2.2511: Insulate bare equipment | $1,694 | $5,068 | - | - |
$1,694
-
MMBtu
|
- | - | |
| 05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $4,820 | $15,700 |
$3,036
59,496
kWh
|
$1,784
-
kW-mo/yr
|
- | - | - | |
| 06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,572 | $8,872 |
$944
18,464
kWh
|
$1,628
-
kW-mo/yr
|
- | - | - | |
| 07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,404 | $19,349 |
$3,252
66,237
kWh
|
$2,152
-
kW-mo/yr
|
- | - | - | |
| 08 | 3.4113: Treat and reuse rinse waters | $1,220 | $4,835 | - | - | - |
$1,220
-
Tgal
|
- | |
| 09 | 4.652: Replace existing equipment with more suitable substitutes | $187,200 | $36,000 | - | - | - | - | $187,200 | |
| 10 | 3.6112: Use filter and drying oven to reduce sludge volume | $2,120 | $6,210 | - | - | - | - | $2,120 | |
| TOTAL RECOMMENDED | $255,520 | $125,416 |
$42,878
841,734
kWh
|
$20,408
-
kW-mo/yr
|
$1,694
-
MMBtu
|
$1,220
-
Tgal
|
$189,320 | ||
| TOTAL IMPLEMENTED | $245,424 | $90,985 |
$38,682
757,033
kWh
|
$16,628
-
kW-mo/yr
|
$1,694
-
MMBtu
|
$1,220
-
Tgal
|
$187,200 | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Water Disposal Savings | Administrative Changes Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs