Assessment Year 1998
Principal Product Custom Printed Material
NAICS
n/a
SIC 2759: Commercial Printing, Not Elsewhere Classified
Sales Range $10
M
to 50
M
# of Employees 300
Plant Area 130,000
ft2
Annual Production 249,600,000
pieces
Production Hrs. Annual 7,488
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $167,659 2,387,163
kWh
Electricity Demand $68,463 6,819
kW-mo/yr
Natural Gas $31,226 5,478
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $97,604 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Solid Waste (non-haz) Savings Primary Raw Material Savings
01 2.8114: Change rate schedules or other changes in utility service $10,516 $240 - - $10,516
-
MMBtu
- - -
02 2.7142: Utilize higher efficiency lamps and/or ballasts $5,893 $2,924 $4,309
61,254
kWh
$1,584
-
kW-mo/yr
- - - -
03 2.7135: Install occupancy sensors $2,197 $1,728 $1,507
21,395
kWh
$690
-
kW-mo/yr
- - - -
04 2.4133: Use most efficient type of electric motors $1,117 $858 $902
12,896
kWh
$215
-
kW-mo/yr
- - - -
05 2.7142: Utilize higher efficiency lamps and/or ballasts $25,307 $36,660 $20,091
286,049
kWh
$5,216
-
kW-mo/yr
- - - -
06 2.7142: Utilize higher efficiency lamps and/or ballasts $8,230 $13,240 $6,694
95,252
kWh
$1,536
-
kW-mo/yr
- - - -
07 2.4111: Utilize energy-efficient belts and other improved mechanisms $259 $702 $155
2,345
kWh
$104
-
kW-mo/yr
- - - -
08 3.5313: Increase amount of waste recovered for resale $5,866 - - - - - $5,866
-
lb
-
09 3.5316: Contract a wood pallet recycling company $3,642 $200 - - - - $3,642
-
lb
-
10 3.6193: Install equipment (eg compactor) to reduce disposal costs $7,861 $8,700 - - - - $7,861
-
lb
-
11 3.5313: Increase amount of waste recovered for resale $12,856 $10,280 - - - - $12,856
-
lb
-
12 3.8143: Recycle cleaning solvent and reuse $13,860 $40,000 - - - $6,160
-
gal
- $7,700
TOTAL RECOMMENDED $97,604 $115,532 $33,658
479,191
kWh
$9,345
-
kW-mo/yr
$10,516
-
MMBtu
$6,160
-
gal
$30,225
-
lb
$7,700
TOTAL IMPLEMENTED - - - - - - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings Electricity Demand Savings Natural Gas Savings Other Liquid (haz) Savings Solid Waste (non-haz) Savings Primary Raw Material Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs