Assessment Year | 1998 |
---|---|
Principal Product | Wood & Upholstery Furniture |
NAICS |
n/a
|
SIC | 2531: Public Building and Related Furniture |
Sales Range | $10 M to 50M |
# of Employees | 118 |
Plant Area |
60,000
ft2
|
Annual Production | 220,000
pieces
|
Production Hrs. Annual | 4,680
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $69,086 | 1,083,236 |
kWh
|
$0.064 |
Electricity Demand | $21,035 | 3,965 |
kW-mo/yr
|
$5.31 |
Natural Gas | $8,448 | 1,268 |
MMBtu
|
$6.66 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $197,535 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $170,132 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Increase in Production Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,673 | - |
$3,394
53,048
kWh
|
$279
-
kW-mo/yr
|
- | - | |
02 | 2.7131: Add area lighting switches | $860 | $90 |
$860
13,482
kWh
|
- | - | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,521 | $1,200 |
$1,028
16,120
kWh
|
$493
-
kW-mo/yr
|
- | - | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $267 | $233 |
$203
3,224
kWh
|
$64
-
kW-mo/yr
|
- | - | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $3,097 | $5,250 |
$2,094
32,825
kWh
|
$1,003
-
kW-mo/yr
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $469 | $905 |
$374
5,862
kWh
|
$95
-
kW-mo/yr
|
- | - | |
07 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,456 | $14,990 |
$4,891
76,788
kWh
|
$1,565
-
kW-mo/yr
|
- | - | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $6,827 | $24,062 |
$6,827
106,975
kWh
|
- | - | - | |
09 | 3.5313: Increase amount of waste recovered for resale | $22,785 | $100 | - | - |
$22,785
-
lb
|
- | |
10 | 4.111: Add equipment/ operators to reduce production bottleneck | $151,580 | $152,960 | - | - | - | $151,580 | |
TOTAL RECOMMENDED | $197,535 | $199,790 |
$19,671
308,324
kWh
|
$3,499
-
kW-mo/yr
|
$22,785
-
lb
|
$151,580 | ||
TOTAL IMPLEMENTED | $170,132 | $193,240 |
$16,549
259,379
kWh
|
$2,003
-
kW-mo/yr
|
- | $151,580 | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings | Increase in Production Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs