Assessment Year | 1997 |
---|---|
Principal Product | Exhibits |
NAICS |
n/a
|
SIC | 2599: Furniture and Fixtures, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 180 |
Plant Area |
280,000
ft2
|
Annual Production | 300
pieces
|
Production Hrs. Annual | 2,600
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $83,553 | 1,027,257 |
kWh
|
$0.081 |
Electricity Demand | $13,345 | 3,380 |
kW-mo/yr
|
$3.95 |
Natural Gas | $10,408 | 1,808 |
MMBtu
|
$5.76 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $17,832 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,021 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|
01 | 2.4133: Use most efficient type of electric motors | $500 | $742 |
$403
4,982
kWh
|
$97
-
kW-mo/yr
|
- | |
02 | 2.6218: Turn off equipment when not in use | $1,849 | $3,760 |
$1,669
20,516
kWh
|
$180
-
kW-mo/yr
|
- | |
03 | 2.7131: Add area lighting switches | $535 | $850 |
$431
5,275
kWh
|
$104
-
kW-mo/yr
|
- | |
04 | 2.7134: Use photocell controls | $1,929 | $1,500 |
$1,556
19,050
kWh
|
$373
-
kW-mo/yr
|
- | |
05 | 2.7133: Use separate switches on perimeter lighting which may be turned off when natural light is available | $970 | $1,500 |
$783
9,672
kWh
|
$187
-
kW-mo/yr
|
- | |
06 | 2.7144: Install spectral reflectors / delamp | $5,094 | $8,069 |
$4,547
55,979
kWh
|
$547
-
kW-mo/yr
|
- | |
07 | 2.7135: Install occupancy sensors | $434 | $1,440 |
$350
4,396
kWh
|
$84
-
kW-mo/yr
|
- | |
08 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $5,081 | $12,944 |
$5,081
62,427
kWh
|
- | - | |
09 | 2.4231: Reduce the pressure of compressed air to the minimum required | $253 | $25 |
$204
2,638
kWh
|
$49
-
kW-mo/yr
|
- | |
10 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $521 | $300 |
$420
5,275
kWh
|
$101
-
kW-mo/yr
|
- | |
11 | 3.5313: Increase amount of waste recovered for resale | $630 | $195 | - | - |
$630
-
lb
|
|
12 | 3.5315: Lease / purchase baler; sell cardboard to recycler | $36 | - | - | - |
$36
-
lb
|
|
TOTAL RECOMMENDED | $17,832 | $31,325 |
$15,444
190,210
kWh
|
$1,722
-
kW-mo/yr
|
$666
-
lb
|
||
TOTAL IMPLEMENTED | $7,021 | $14,206 |
$6,108
75,322
kWh
|
$247
-
kW-mo/yr
|
$666
-
lb
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs