Assessment Year | 1996 |
---|---|
Principal Product | Stainless Steel Gas Panel Tubing Assemblies |
NAICS |
n/a
|
SIC | 3499: Fabricated Metal Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 250 |
Plant Area |
47,000
ft2
|
Annual Production | 720,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $179,954 | 1,939,332 |
kWh
|
$0.093 |
Electricity Demand | $12,832 | 2,969 |
kW-mo/yr
|
$4.32 |
Natural Gas | $1,561 | 192 |
MMBtu
|
$8.13 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $50,561 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $17,141 | $19,207 |
$17,141
140,094
kWh
|
- | - | - | |
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $9,293 | $6,804 |
$16,188
132,474
kWh
|
- |
$(-6,895.0)
-
MMBtu
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $725 | $595 |
$712
6,741
kWh
|
$13
-
kW-mo/yr
|
- | - | |
04 | 2.6218: Turn off equipment when not in use | $3,216 | $2,840 |
$3,216
26,377
kWh
|
- | - | - | |
05 | 2.7144: Install spectral reflectors / delamp | $3,017 | $6,950 |
$2,868
25,791
kWh
|
$149
-
kW-mo/yr
|
- | - | |
06 | 2.2514: Cover open tanks | $10,274 | $1,400 |
$10,274
84,115
kWh
|
- | - | - | |
07 | 3.6193: Install equipment (eg compactor) to reduce disposal costs | $6,895 | $6,395 | - | - | - |
$6,895
-
lb
|
|
TOTAL RECOMMENDED | $50,561 | $44,191 |
$50,399
415,592
kWh
|
$162
-
kW-mo/yr
|
$(-6,895.0)
-
MMBtu
|
$6,895
-
lb
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | Solid Waste (non-haz) Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs