Assessment Year 1995
Principal Product Finished Wood Door Stock
NAICS
n/a
SIC 2421: Sawmills and Planing Mills, General
Sales Range $10
M
to 50
M
# of Employees 85
Plant Area 59,200
ft2
Annual Production 7,800
thousand feet
Production Hrs. Annual 4,160
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $226,063 1,991,794
kWh
Natural Gas $4,488 701
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $41,350 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* -

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings
01 2.4133: Use most efficient type of electric motors $1,195 $1,746 n/a $1,195
10,551
kWh
02 2.7142: Utilize higher efficiency lamps and/or ballasts $1,404 $4,680 n/a $1,404
12,309
kWh
03 2.7134: Use photocell controls $1,710 $3,150 n/a $1,710
14,947
kWh
04 2.3212: Optimize plant power factor $2,222 $3,227 n/a $2,222
-
kWh
05 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $23,877 $94,943 n/a $23,877
210,434
kWh
06 2.6218: Turn off equipment when not in use $831 $1,380 n/a $831
7,327
kWh
07 2.3131: Reschedule plant operations or reduce load to avoid peaks $565 - n/a $565
-
kWh
08 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves $2,592 - n/a $2,592
28,136
kWh
09 2.4231: Reduce the pressure of compressed air to the minimum required $1,744 $3,255 n/a $1,744
15,240
kWh
10 2.4111: Utilize energy-efficient belts and other improved mechanisms $5,210 $854 n/a $5,210
46,014
kWh
TOTAL RECOMMENDED $41,350 $113,235 $41,350
344,958
kWh
TOTAL IMPLEMENTED - - -
Yearly Savings* Imp'd Cost* Electricity Usage Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs