Assessment Year 1994
Principal Product Candy
NAICS
n/a
SIC 2064: Candy and Other Confectionery Products
Sales Range $10
M
to 50
M
# of Employees 200
Plant Area 210,000
ft2
Annual Production 25,000,000
lb
Production Hrs. Annual 4,144
hrs
Location (State) California

Facility Energy Cost and Usage

Source Yearly Cost Usage
Electricity Usage $640,059 7,902,990
kWh
Natural Gas $167,892 49,359
MMBtu
TOTAL YEARLY COSTS -
RECOMMENDED SAVINGS* $462,686 *Non-energy impacts included in savings.
IMPLEMENTED SAVINGS* $63,533

Recommendations

# Description Yearly Savings* Imp'd Cost* Status Electricity Usage Savings Natural Gas Savings
01 2.4133: Use most efficient type of electric motors $20,615 $15,734 $20,615
254,689
kWh
-
02 2.7142: Utilize higher efficiency lamps and/or ballasts $7,091 $12,697 $7,091
87,632
kWh
-
03 2.7135: Install occupancy sensors $11,565 $13,467 $11,565
142,732
kWh
-
04 2.4146: Use adjustable frequency drive or multiple speed motors on existing system $7,728 $10,400 $7,728
95,545
kWh
-
05 2.3212: Optimize plant power factor $3,399 $6,386 $3,399
-
kWh
-
06 2.5194: Redesign process $4,700 $15,500 - $4,700
-
MMBtu
07 2.4231: Reduce the pressure of compressed air to the minimum required $1,105 $5,500 $1,105
13,775
kWh
-
08 2.6218: Turn off equipment when not in use $4,300 $200 $4,300
53,048
kWh
-
09 2.1233: Analyze flue gas for proper air/fuel ratio $3,030 - - $3,030
-
MMBtu
10 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat $399,153 $979,000 $464,337
6,072,685
kWh
$(-65,184.0)
-
MMBtu
TOTAL RECOMMENDED $462,686 $1,058,884 $520,140
6,720,106
kWh
$(-57,454.0)
-
MMBtu
TOTAL IMPLEMENTED $63,533 $79,884 $55,803
647,421
kWh
$7,730
-
MMBtu
Yearly Savings* Imp'd Cost* Electricity Usage Savings Natural Gas Savings
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs