Assessment Year | 1994 |
---|---|
Principal Product | Plastic Packaging |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $1 M to 5M |
# of Employees | 50 |
Plant Area |
25,000
ft2
|
Annual Production | 200,000
ton
|
Production Hrs. Annual | 6,120
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $175,626 | 1,612,837 |
kWh
|
$0.11 |
Natural Gas | $2,273 | 255 |
MMBtu
|
$8.91 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $24,172 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $17,623 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.4239: Eliminate or reduce compressed air usage | $8,700 | $12,500 |
$8,700
80,012
kWh
|
|
02 | 2.2511: Insulate bare equipment | $6,549 | $520 |
$6,549
60,082
kWh
|
|
03 | 2.4133: Use most efficient type of electric motors | $4,671 | $3,216 |
$4,671
43,083
kWh
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $1,449 | $2,110 |
$1,449
13,189
kWh
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $1,245 | $2,128 |
$1,245
11,430
kWh
|
|
06 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $1,207 | $520 |
$1,207
11,137
kWh
|
|
07 | 2.7135: Install occupancy sensors | $351 | $735 |
$351
3,224
kWh
|
|
TOTAL RECOMMENDED | $24,172 | $21,729 |
$24,172
222,157
kWh
|
||
TOTAL IMPLEMENTED | $17,623 | $21,209 |
$17,623
162,075
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs