Assessment Year | 1993 |
---|---|
Principal Product | Custom Molded Plastics and Cork |
NAICS |
n/a
|
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 110 |
Plant Area |
140,000
ft2
|
Annual Production | 4,000
ton
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $389,715 | 4,210,434 |
kWh
|
$0.093 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $81,157 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $13,163 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings |
---|---|---|---|---|---|
01 | 2.2511: Insulate bare equipment | $18,225 | $2,514 |
$18,225
197,245
kWh
|
|
02 | 2.4133: Use most efficient type of electric motors | $9,017 | $4,460 |
$9,017
97,304
kWh
|
|
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $2,329 | $3,611 |
$2,329
25,205
kWh
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $1,817 | $600 |
$1,817
19,637
kWh
|
|
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $2,548 | $550 |
$2,548
27,550
kWh
|
|
06 | 2.8114: Change rate schedules or other changes in utility service | $44,008 | $149,000 |
$44,008
-
kWh
|
|
07 | 2.3212: Optimize plant power factor | $3,213 | $5,507 |
$3,213
-
kWh
|
|
TOTAL RECOMMENDED | $81,157 | $166,242 |
$81,157
366,941
kWh
|
||
TOTAL IMPLEMENTED | $13,163 | $8,671 |
$13,163
142,146
kWh
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs