Assessment Year | 2020 |
---|---|
Principal Product | Server Cabinets |
NAICS | 332321: Metal Window and Door Manufacturing |
SIC | 3444: Sheet Metal Work |
Sales Range | $10 M to 50M |
# of Employees | 86 |
Plant Area |
58,000
ft2
|
Annual Production | 21,000
units
|
Production Hrs. Annual | 4,335
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $99,033 | 815,130 |
kWh
|
$0.12 |
Electricity Demand | $33,030 | 2,804 |
kW-mo/yr
|
$11.78 |
Electricity Fees | $2,889 | - |
|
- |
Natural Gas | $71,939 | 10,235 |
MMBtu
|
$7.03 |
TOTAL YEARLY COSTS | $206,891 | |||
RECOMMENDED SAVINGS* | $20,185 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,809 | $30,150 |
$8,052
66,278
kWh
|
$3,757
-
kW-mo/yr
|
|
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $3,628 | $300 |
$3,201
26,331
kWh
|
$427
-
kW-mo/yr
|
|
03 | 2.4324: Replace hydraulic / pneumatic equipment with electric equipment | $3,037 | $2,560 |
$3,037
24,999
kWh
|
- | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,711 | - |
$1,711
14,092
kWh
|
- | |
TOTAL RECOMMENDED | $20,185 | $33,010 |
$16,001
131,700
kWh
|
$4,184
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs