Assessment Year | 2018 |
---|---|
Principal Product | Plastic Containers |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 80 |
Plant Area |
80,000
ft2
|
Annual Production | 300,000,000
units
|
Production Hrs. Annual | 6,000
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $323,527 | 4,812,782 |
kWh
|
$0.067 |
Electricity Demand | $266,002 | 13,608 |
kW-mo/yr
|
$19.55 |
Electricity Fees | $9,454 | - |
|
- |
Natural Gas | $3,915 | 448 |
MMBtu
|
$8.73 |
TOTAL YEARLY COSTS | $602,898 | |||
RECOMMENDED SAVINGS* | $62,701 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1336: Install equipment to utilize waste fuel | $35,866 | $178,055 |
$6,135
91,313
kWh
|
$29,731
-
kW-mo/yr
|
- | |
02 | 2.7425: Clean or color roof to reduce solar load | $20,104 | $28,000 |
$15,499
230,635
kWh
|
$4,605
-
kW-mo/yr
|
- | |
03 | 2.2511: Insulate bare equipment | $3,128 | $939 | - | - |
$3,128
-
MMBtu
|
|
04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,822 | $2,000 |
$2,822
42,000
kWh
|
- | - | |
05 | 2.4133: Use most efficient type of electric motors | $781 | $3,825 |
$781
11,620
kWh
|
- | - | |
TOTAL RECOMMENDED | $62,701 | $212,819 |
$25,237
375,568
kWh
|
$34,336
-
kW-mo/yr
|
$3,128
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs