Assessment Year | 2018 |
---|---|
Principal Product | Salad Toppings |
NAICS | 311812: Commercial Bakeries |
SIC | 2051: Bread and Other Bakery Products, Except Cookies and Crackers |
Sales Range | $100 M to 500M |
# of Employees | 240 |
Plant Area |
515,000
ft2
|
Annual Production | 45,000,000
lb
|
Production Hrs. Annual | 5,304
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $300,521 | 3,649,619 |
kWh
|
$0.082 |
Electricity Demand | $179,672 | 8,819 |
kW-mo/yr
|
$20.37 |
Electricity Fees | $6,709 | - |
|
- |
Natural Gas | $283,818 | 50,420 |
MMBtu
|
$5.63 |
TOTAL YEARLY COSTS | $770,720 | |||
RECOMMENDED SAVINGS* | $81,427 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $22,592 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Ancillary Material Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.1336: Install equipment to utilize waste fuel | $53,280 | $265,840 |
$11,877
144,310
kWh
|
$41,403
-
kW-mo/yr
|
- | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $13,921 | $2,000 |
$13,921
169,153
kWh
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,832 | $13,363 |
$3,542
43,039
kWh
|
$2,204
-
kW-mo/yr
|
$86 | |
04 | 2.4231: Reduce the pressure of compressed air to the minimum required | $5,555 | $6,800 |
$5,555
67,493
kWh
|
- | - | |
05 | 2.7134: Use photocell controls | $2,839 | $11,100 |
$2,839
34,498
kWh
|
- | - | |
TOTAL RECOMMENDED | $81,427 | $299,103 |
$37,734
458,493
kWh
|
$43,607
-
kW-mo/yr
|
$86 | ||
TOTAL IMPLEMENTED | $22,592 | $26,463 |
$20,302
246,690
kWh
|
$2,204
-
kW-mo/yr
|
$86 |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs