Assessment Year | 2017 |
---|---|
Principal Product | Sausages and Other Prepared Meats |
NAICS | 311612: Meat Processed from Carcasses |
SIC | 2013: Sausages and Other Prepared Meat Products |
Sales Range | $50 M to 100M |
# of Employees | 200 |
Plant Area |
100,000
ft2
|
Annual Production | 35,000,000
lb
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $469,239 | 4,910,946 |
kWh
|
$0.096 |
Electricity Demand | $185,102 | 10,651 |
kW-mo/yr
|
$17.38 |
Electricity Fees | $39,190 | - |
|
- |
Natural Gas | $76,766 | 21,633 |
MMBtu
|
$3.55 |
TOTAL YEARLY COSTS | $770,297 | |||
RECOMMENDED SAVINGS* | $317,037 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $19,127 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $289,101 | $1,166,652 |
$297,215
3,112,200
kWh
|
$104,019
-
kW-mo/yr
|
$(-62,244.0) |
$(-49,889.0)
-
MMBtu
|
|
02 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $8,037 | $28,000 |
$3,793
39,718
kWh
|
$4,244
-
kW-mo/yr
|
- | - | |
03 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,649 | $9,540 |
$4,924
51,590
kWh
|
$1,725
-
kW-mo/yr
|
- | - | |
04 | 2.4133: Use most efficient type of electric motors | $5,984 | $18,111 |
$4,408
46,163
kWh
|
$1,576
-
kW-mo/yr
|
- | - | |
05 | 2.2135: Repair and eliminate steam leaks | $4,167 | $600 | - | - | - |
$4,167
-
MMBtu
|
|
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,327 | $1,500 |
$1,802
18,870
kWh
|
$525
-
kW-mo/yr
|
- | - | |
07 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $496 | $1,765 |
$394
4,121
kWh
|
$102
-
kW-mo/yr
|
- | - | |
08 | 2.4239: Eliminate or reduce compressed air usage | $276 | $800 |
$257
2,693
kWh
|
$19
-
kW-mo/yr
|
- | - | |
TOTAL RECOMMENDED | $317,037 | $1,226,968 |
$312,793
3,275,355
kWh
|
$112,210
-
kW-mo/yr
|
$(-62,244.0) |
$(-45,722.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $19,127 | $29,751 |
$11,134
116,623
kWh
|
$3,826
-
kW-mo/yr
|
- |
$4,167
-
MMBtu
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs