Assessment Year | 2016 |
---|---|
Principal Product | High Performance Catalysts and Resins, Research and Development |
NAICS | 325180: Other Basic Inorganic Chemical Manufacturing |
SIC | 2819: Industrial Inorganic Chemicals, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 110 |
Plant Area |
65,000
ft2
|
Annual Production | 11,000
lb
|
Production Hrs. Annual | 3,900
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $203,943 | 1,748,230 |
kWh
|
$0.12 |
Electricity Demand | $65,108 | 4,610 |
kW-mo/yr
|
$14.12 |
Electricity Fees | $63,626 | - |
|
- |
Natural Gas | $14,268 | 1,826 |
MMBtu
|
$7.81 |
TOTAL YEARLY COSTS | $346,945 | |||
RECOMMENDED SAVINGS* | $78,797 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $7,718 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
---|---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $23,109 | $108,180 |
$16,290
139,589
kWh
|
$6,819
-
kW-mo/yr
|
- | |
02 | 2.7491: Insulate glazing, walls, ceilings, and roofs | $21,873 | $21,829 |
$18,258
156,455
kWh
|
$3,615
-
kW-mo/yr
|
- | |
03 | 2.3212: Optimize plant power factor | $10,293 | $10,000 | - | - | $10,293 | |
04 | 2.7121: Utilize daylight whenever possible in lieu of artificial light | $9,320 | $22,960 |
$5,980
51,249
kWh
|
$3,340
-
kW-mo/yr
|
- | |
05 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $6,406 | $10,314 |
$4,387
37,588
kWh
|
$2,019
-
kW-mo/yr
|
- | |
06 | 2.7423: Reduce heat gain by window tinting | $2,089 | $7,880 |
$1,657
14,203
kWh
|
$432
-
kW-mo/yr
|
- | |
07 | 2.4131: Size electric motors for peak operating efficiency | $1,758 | $5,550 |
$1,281
10,982
kWh
|
$477
-
kW-mo/yr
|
- | |
08 | 2.7134: Use photocell controls | $1,432 | $4,070 |
$1,337
11,450
kWh
|
$95
-
kW-mo/yr
|
- | |
09 | 2.7135: Install occupancy sensors | $1,312 | $3,610 |
$1,312
11,240
kWh
|
- | - | |
10 | 2.7312: Minimize use of outside make-up air for ventilation except when used for economizer cycle | $1,205 | $2,550 |
$928
7,954
kWh
|
$277
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $78,797 | $196,943 |
$51,430
440,710
kWh
|
$17,074
-
kW-mo/yr
|
$10,293 | ||
TOTAL IMPLEMENTED | $7,718 | $13,924 |
$5,699
48,828
kWh
|
$2,019
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs