Assessment Year | 2016 |
---|---|
Principal Product | Color Printing |
NAICS | 323111: Commercial Printing (except Screen and Books) |
SIC | 2752: Commercial Printing, Lithographic |
Sales Range | $10 M to 50M |
# of Employees | 73 |
Plant Area |
30,000
ft2
|
Annual Production | 6,000
units
|
Production Hrs. Annual | 4,590
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $133,261 | 1,311,664 |
kWh
|
$0.10 |
Electricity Demand | $274,311 | 7,159 |
kW-mo/yr
|
$38.32 |
Electricity Fees | $34,902 | - |
|
- |
TOTAL YEARLY COSTS | $442,474 | |||
RECOMMENDED SAVINGS* | $48,021 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $18,276 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7241: Install outside air damper / economizer on hvac unit | $17,516 | $28,660 |
$14,052
138,306
kWh
|
$3,464
-
kW-mo/yr
|
|
02 | 2.7228: Avoid introducing hot, humid, or dirty air into hvac system | $12,021 | $5,775 |
$5,698
56,083
kWh
|
$6,323
-
kW-mo/yr
|
|
03 | 2.7423: Reduce heat gain by window tinting | $5,102 | $15,750 |
$2,853
28,081
kWh
|
$2,249
-
kW-mo/yr
|
|
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $5,898 | $9,052 |
$2,809
27,660
kWh
|
$3,089
-
kW-mo/yr
|
|
05 | 2.2693: Use waste heat steam for absorption refrigeration | $2,674 | $2,863 |
$1,459
14,363
kWh
|
$1,215
-
kW-mo/yr
|
|
06 | 2.7134: Use photocell controls | $2,143 | $1,850 |
$1,135
11,173
kWh
|
$1,008
-
kW-mo/yr
|
|
07 | 2.4133: Use most efficient type of electric motors | $1,762 | $3,097 |
$880
8,664
kWh
|
$882
-
kW-mo/yr
|
|
08 | 2.4231: Reduce the pressure of compressed air to the minimum required | $357 | $200 |
$357
3,510
kWh
|
- | |
09 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $548 | $180 |
$276
2,712
kWh
|
$272
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $48,021 | $67,427 |
$29,519
290,552
kWh
|
$18,502
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $18,276 | $15,027 |
$8,864
87,253
kWh
|
$9,412
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs