Assessment Year | 2016 |
---|---|
Principal Product | Electronics testing platforms |
NAICS | 334515: Instrument Manufacturing for Measuring and Testing Electricity and Electrical Signals |
SIC | 3825: Instruments for Measuring and Testing of Electricity and Electrical Signals |
Sales Range | $100 M to 500M |
# of Employees | 400 |
Plant Area |
330,000
ft2
|
Annual Production | 400
pieces
|
Production Hrs. Annual | 6,864
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $723,468 | 6,348,364 |
kWh
|
$0.11 |
Electricity Demand | $430,707 | 15,461 |
kW-mo/yr
|
$27.86 |
Electricity Fees | $4,407 | - |
|
- |
Natural Gas | $7,280 | 902 |
MMBtu
|
$8.07 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $251,379 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $16,878 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
---|---|---|---|---|---|---|---|
01 | 2.1336: Install equipment to utilize waste fuel | $116,648 | $532,759 |
$66,728
593,666
kWh
|
$49,920
-
kW-mo/yr
|
- | |
02 | 2.7232: Replace existing hvac unit with high efficiency model | $69,647 | $181,800 |
$41,529
369,476
kWh
|
$28,118
-
kW-mo/yr
|
- | |
03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $14,569 | $4,000 |
$8,501
75,625
kWh
|
$6,068
-
kW-mo/yr
|
- | |
04 | 2.7142: Utilize higher efficiency lamps and/or ballasts | $14,433 | $30,898 |
$10,438
92,868
kWh
|
$4,620
-
kW-mo/yr
|
$(-625.0) | |
05 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $13,124 | $7,975 |
$9,213
81,966
kWh
|
$3,911
-
kW-mo/yr
|
- | |
06 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,814 | $18,199 |
$8,727
77,645
kWh
|
$3,087
-
kW-mo/yr
|
- | |
07 | 2.4231: Reduce the pressure of compressed air to the minimum required | $4,363 | $800 |
$4,363
38,817
kWh
|
- | - | |
08 | 2.7135: Install occupancy sensors | $3,754 | $1,310 |
$3,754
33,393
kWh
|
- | - | |
09 | 2.7292: Lower ceiling to reduce conditioned space | $2,073 | $5,877 |
$1,379
12,281
kWh
|
$694
-
kW-mo/yr
|
- | |
10 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $954 | $2,390 |
$954
8,487
kWh
|
- | - | |
TOTAL RECOMMENDED | $251,379 | $786,008 |
$155,586
1,384,224
kWh
|
$96,418
-
kW-mo/yr
|
$(-625.0) | ||
TOTAL IMPLEMENTED | $16,878 | $9,285 |
$12,967
115,359
kWh
|
$3,911
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | One-time Revenue or Avoided Cost Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs