Assessment Year | 2015 |
---|---|
Principal Product | injection molded plastic parts |
NAICS | 326199: All Other Plastics Product Manufacturing |
SIC | 3089: Plastics Products, Not Elsewhere Classified |
Sales Range | $10 M to 50M |
# of Employees | 226 |
Plant Area |
50,000
ft2
|
Annual Production | 2,500,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $284,469 | 2,884,857 |
kWh
|
$0.099 |
Electricity Demand | $77,794 | 6,767 |
kW-mo/yr
|
$11.50 |
Electricity Fees | $80,305 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $40,394 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $37,988 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 2.7232: Replace existing hvac unit with high efficiency model | $21,830 | $48,900 |
$18,720
189,870
kWh
|
$3,110
-
kW-mo/yr
|
|
02 | 2.7224: Reduce space conditioning during non-working hours | $12,584 | $3,900 |
$12,584
220,022
kWh
|
- | |
03 | 2.7135: Install occupancy sensors | $2,406 | $2,370 |
$2,406
24,386
kWh
|
- | |
04 | 2.7134: Use photocell controls | $1,539 | $1,295 |
$1,539
15,627
kWh
|
- | |
05 | 2.4231: Reduce the pressure of compressed air to the minimum required | $1,238 | $200 |
$1,238
12,553
kWh
|
- | |
06 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $797 | $1,500 |
$645
6,538
kWh
|
$152
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $40,394 | $58,165 |
$37,132
468,996
kWh
|
$3,262
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $37,988 | $55,795 |
$34,726
444,610
kWh
|
$3,262
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs