Assessment Year | 2015 |
---|---|
Principal Product | aircraft structures |
NAICS | 332312: Fabricated Structural Metal Manufacturing |
SIC | 3441: Fabricated Structural Metal |
Sales Range | $50 M to 100M |
# of Employees | 500 |
Plant Area |
1,150,000
ft2
|
Annual Production | 50,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,628,052 | 21,827,094 |
kWh
|
$0.075 |
Electricity Demand | $716,901 | 46,063 |
kW-mo/yr
|
$15.56 |
Electricity Fees | $169,215 | - |
|
- |
Natural Gas | $218,442 | 31,217 |
MMBtu
|
$7.00 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $444,762 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | - |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.3415: Use a fossil fuel engine to cogenerate electricity or motive power; and utilize heat | $209,960 | $1,040,000 |
$210,385
3,853,200
kWh
|
$121,368
-
kW-mo/yr
|
$(-121,793.0)
-
MMBtu
|
|
02 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $163,675 | $32,788 |
$147,736
1,980,379
kWh
|
$75,061
-
kW-mo/yr
|
$(-59,122.0)
-
MMBtu
|
|
03 | 2.7232: Replace existing hvac unit with high efficiency model | $49,380 | $151,600 |
$32,173
431,281
kWh
|
$17,207
-
kW-mo/yr
|
- | |
04 | 2.4321: Upgrade obsolete equipment | $9,105 | $25,000 |
$7,078
94,881
kWh
|
$2,027
-
kW-mo/yr
|
- | |
05 | 2.4322: Use or replace with energy efficient substitutes | $5,959 | $12,000 |
$5,959
79,886
kWh
|
- | - | |
06 | 2.4133: Use most efficient type of electric motors | $3,564 | $5,290 |
$2,317
31,037
kWh
|
$1,247
-
kW-mo/yr
|
- | |
07 | 2.4239: Eliminate or reduce compressed air usage | $1,240 | $1,550 |
$530
7,110
kWh
|
$710
-
kW-mo/yr
|
- | |
08 | 2.4323: Use optimum size and capacity equipment | $948 | $3,375 |
$(-569.0)
(-7,622)
kWh
|
$(-163.0)
-
kW-mo/yr
|
$1,680
-
MMBtu
|
|
09 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $931 | $3,050 |
$668
8,960
kWh
|
$263
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $444,762 | $1,274,653 |
$406,277
6,479,112
kWh
|
$217,720
-
kW-mo/yr
|
$(-179,235.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | - | - | - | - | - | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs