| Assessment Year | 2015 |
|---|---|
| Principal Product | Aircraft components |
| NAICS | 332112: Nonferrous Forging |
| SIC | 3463: Nonferrous Forgings |
| Sales Range | $10 M to 50M |
| # of Employees | 45 |
| Plant Area |
80,000
ft2
|
| Annual Production | 100
pieces
|
| Production Hrs. Annual | 5,860
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $134,244 | 1,562,182 |
kWh
|
$0.086 |
| Electricity Demand | $121,635 | 6,202 |
kW-mo/yr
|
$19.61 |
| Electricity Fees | $8,865 | - |
|
- |
| Natural Gas | $228,948 | 186,750 |
MMBtu
|
$1.23 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $29,395 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | - | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|---|
| 01 | 2.2414: Use waste heat from hot flue gases to preheat | $12,106 | $21,000 | - | - | - |
$12,106
-
MMBtu
|
|
| 02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $9,418 | $1,750 | - | - | $9,418 | - | |
| 03 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,658 | $2,000 |
$1,373
15,979
kWh
|
$1,285
-
kW-mo/yr
|
- | - | |
| 04 | 2.4133: Use most efficient type of electric motors | $2,296 | $6,475 |
$1,118
13,012
kWh
|
$1,178
-
kW-mo/yr
|
- | - | |
| 05 | 2.7135: Install occupancy sensors | $2,105 | $1,508 |
$2,105
24,500
kWh
|
- | - | - | |
| 06 | 2.2511: Insulate bare equipment | $812 | $2,323 | - | - | - |
$812
-
MMBtu
|
|
| TOTAL RECOMMENDED | $29,395 | $35,056 |
$4,596
53,491
kWh
|
$2,463
-
kW-mo/yr
|
$9,418 |
$12,918
-
MMBtu
|
||
| TOTAL IMPLEMENTED | - | - | - | - | - | - | ||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Electricity Fees Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs