Assessment Year | 2015 |
---|---|
Principal Product | Envelopes |
NAICS | 322230: Stationery Product Manufacturing |
SIC | 2677: Envelopes |
Sales Range | $50 M to 100M |
# of Employees | 240 |
Plant Area |
185,000
ft2
|
Annual Production | 4,000,000,000
pieces
|
Production Hrs. Annual | 6,240
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,031,885 | 12,625,403 |
kWh
|
$0.082 |
Electricity Demand | $717,512 | 27,094 |
kW-mo/yr
|
$26.48 |
Electricity Fees | $78,693 | - |
|
- |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $44,891 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $38,474 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
---|---|---|---|---|---|---|
01 | 3.1192: Reduce scrap production | $19,598 | $28,920 |
$19,598
239,883
kWh
|
- | |
02 | 2.7135: Install occupancy sensors | $10,167 | $7,660 |
$10,167
124,438
kWh
|
- | |
03 | 2.4133: Use most efficient type of electric motors | $5,931 | $9,450 |
$3,662
44,817
kWh
|
$2,269
-
kW-mo/yr
|
|
04 | 2.7232: Replace existing hvac unit with high efficiency model | $4,415 | $13,500 |
$2,535
31,025
kWh
|
$1,880
-
kW-mo/yr
|
|
05 | 2.4111: Utilize energy-efficient belts and other improved mechanisms | $2,778 | $864 |
$1,692
20,695
kWh
|
$1,086
-
kW-mo/yr
|
|
06 | 2.3132: Recharge batteries on during off-peak demand periods | $2,002 | $500 | - |
$2,002
-
kW-mo/yr
|
|
TOTAL RECOMMENDED | $44,891 | $60,894 |
$37,654
460,858
kWh
|
$7,237
-
kW-mo/yr
|
||
TOTAL IMPLEMENTED | $38,474 | $46,894 |
$35,119
429,833
kWh
|
$3,355
-
kW-mo/yr
|
||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs