Assessment Year | 2011 |
---|---|
Principal Product | Explosive Ordinance |
NAICS | 332993: Ammunition (except Small Arms) Manufacturing |
SIC | 3483: Ammunition, Except for Small Arms |
Sales Range | $50 M to 100M |
# of Employees | 341 |
Plant Area |
125,904
ft2
|
Annual Production | 9,845,856
pieces
|
Production Hrs. Annual | 7,280
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $1,356,242 | 11,669,600 |
kWh
|
$0.12 |
Electricity Demand | $74,074 | 26,936 |
kW-mo/yr
|
$2.75 |
Electricity Fees | $40,691 | - |
|
- |
Natural Gas | $566,119 | 78,481 |
MMBtu
|
$7.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $63,354 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $20,022 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.4231: Reduce the pressure of compressed air to the minimum required | $6,430 | - |
$6,430
55,335
kWh
|
- | - | |
02 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $20,022 | $2,400 |
$20,022
167,116
kWh
|
- | - | |
03 | 2.4146: Use adjustable frequency drive or multiple speed motors on existing system | $11,899 | $10,561 |
$11,517
99,115
kWh
|
$382
-
kW-mo/yr
|
- | |
04 | 2.4133: Use most efficient type of electric motors | $17,230 | $18,098 |
$16,490
141,916
kWh
|
$740
-
kW-mo/yr
|
- | |
05 | 2.4112: Install soft-start to eliminate nuisance trips | $7,773 | $17,794 |
$(-3,254.0)
(-28,007)
kWh
|
$(-104.0)
-
kW-mo/yr
|
$11,131
-
MMBtu
|
|
TOTAL RECOMMENDED | $63,354 | $48,853 |
$51,205
435,475
kWh
|
$1,018
-
kW-mo/yr
|
$11,131
-
MMBtu
|
||
TOTAL IMPLEMENTED | $20,022 | $2,400 |
$20,022
167,116
kWh
|
- | - |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs