| Assessment Year | 2010 |
|---|---|
| Principal Product | Vinyl Composition Tile |
| NAICS | 326199: All Other Plastics Product Manufacturing |
| SIC | 3996: Linoleum, Asphalted-Felt-Base, and Other Hard Surface Floor Coverings, Not Elsewhere Classified |
| Sales Range | $100 M to 500M |
| # of Employees | 131 |
| Plant Area |
250,000
ft2
|
| Annual Production | 3,000,000
units
|
| Production Hrs. Annual | 5,880
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $1,412,058 | 16,911,922 |
kWh
|
$0.083 |
| Electricity Demand | $644,355 | 45,096 |
kW-mo/yr
|
$14.29 |
| Electricity Fees | $(-217,193.0) | - |
|
- |
| Natural Gas | $313,208 | 46,775 |
MMBtu
|
$6.70 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $94,638 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $94,638 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings |
|---|---|---|---|---|---|---|
| 01 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $33,987 | $2,250 |
$25,185
301,681
kWh
|
$8,802
-
kW-mo/yr
|
|
| 02 | 2.4133: Use most efficient type of electric motors | $28,203 | $56,758 |
$20,430
244,671
kWh
|
$7,773
-
kW-mo/yr
|
|
| 03 | 2.7124: Make a practice of turning off lights when not needed | $24,981 | - |
$13,335
159,703
kWh
|
$11,646
-
kW-mo/yr
|
|
| 04 | 2.7145: Install skylights | $7,467 | $22,980 |
$5,538
66,324
kWh
|
$1,929
-
kW-mo/yr
|
|
| TOTAL RECOMMENDED | $94,638 | $81,988 |
$64,488
772,379
kWh
|
$30,150
-
kW-mo/yr
|
||
| TOTAL IMPLEMENTED | $94,638 | $81,988 |
$64,488
772,379
kWh
|
$30,150
-
kW-mo/yr
|
||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs