| Assessment Year | 2015 |
|---|---|
| Principal Product | Corrugated paper boxes |
| NAICS | 322211: Corrugated and Solid Fiber Box Manufacturing |
| SIC | 2653: Corrugated and Solid Fiber Boxes |
| Sales Range | $10 M to 50M |
| # of Employees | 43 |
| Plant Area |
245,000
ft2
|
| Annual Production | 80,001
pieces
|
| Production Hrs. Annual | 4,160
hrs
|
| Location (State) | California |
Facility Energy Cost and Usage
| Source | Yearly Cost | Usage | Unit Cost | |
|---|---|---|---|---|
| Electricity Usage | $125,811 | 1,642,073 |
kWh
|
$0.077 |
| Electricity Demand | $75,710 | 4,664 |
kW-mo/yr
|
$16.23 |
| Electricity Fees | $17,403 | - |
|
- |
| Natural Gas | $234,913 | 36,526 |
MMBtu
|
$6.43 |
| TOTAL YEARLY COSTS | - | |||
| RECOMMENDED SAVINGS* | $46,005 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
| IMPLEMENTED SAVINGS* | $20,247 | |||
Recommendations
| # | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
|---|---|---|---|---|---|---|---|
| 01 | 2.2135: Repair and eliminate steam leaks | $14,239 | $1,000 | - | - |
$14,239
-
MMBtu
|
|
| 02 | 2.2414: Use waste heat from hot flue gases to preheat | $14,048 | $21,000 | - | - |
$14,048
-
MMBtu
|
|
| 03 | 2.2162: Reduce excess steam bleeding | $10,701 | $14,842 | - | - |
$10,701
-
MMBtu
|
|
| 04 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $2,814 | $500 |
$1,746
22,797
kWh
|
$1,068
-
kW-mo/yr
|
- | |
| 05 | 2.2121: Increase amount of condensate returned | $3,194 | $8,000 | - | - |
$3,194
-
MMBtu
|
|
| 06 | 2.7134: Use photocell controls | $1,009 | $440 |
$788
10,250
kWh
|
$221
-
kW-mo/yr
|
- | |
| TOTAL RECOMMENDED | $46,005 | $45,782 |
$2,534
33,047
kWh
|
$1,289
-
kW-mo/yr
|
$42,182
-
MMBtu
|
||
| TOTAL IMPLEMENTED | $20,247 | $9,500 |
$1,746
22,797
kWh
|
$1,068
-
kW-mo/yr
|
$17,433
-
MMBtu
|
||
| Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings | |||
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs