Assessment Year | 2014 |
---|---|
Principal Product | composite layup tooling |
NAICS | 333514: Special Die and Tool, Die Set, Jig, and Fixture Manufacturing |
SIC | 3544: Special Dies and Tools, Die Sets, Jigs and Fixtures, and Industrial Molds |
Sales Range | $50 M to 100M |
# of Employees | 65 |
Plant Area |
24,000
ft2
|
Annual Production | 10,000
pieces
|
Production Hrs. Annual | 7,488
hrs
|
Location (State) | California |
Facility Energy Cost and Usage
Source | Yearly Cost | Usage | Unit Cost | |
---|---|---|---|---|
Electricity Usage | $201,492 | 2,852,641 |
kWh
|
$0.071 |
Electricity Demand | $292,673 | 14,579 |
kW-mo/yr
|
$20.07 |
Electricity Fees | $43,766 | - |
|
- |
Natural Gas | $57,296 | 9,228 |
MMBtu
|
$6.21 |
TOTAL YEARLY COSTS | - | |||
RECOMMENDED SAVINGS* | $196,589 |
See individual recommendations below
*Non-energy impacts included in savings.
|
||
IMPLEMENTED SAVINGS* | $79,501 |
Recommendations
# | Description | Yearly Savings* | Imp'd Cost* | Status | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
---|---|---|---|---|---|---|---|
01 | 2.1311: Replace electrically-operated equipment with fossil fuel equipment | $117,088 | $25,225 |
$2,376
33,657
kWh
|
$115,603
-
kW-mo/yr
|
$(-891.0)
-
MMBtu
|
|
02 | 2.3131: Reschedule plant operations or reduce load to avoid peaks | $31,720 | $5,000 | - |
$31,720
-
kW-mo/yr
|
- | |
03 | 2.7232: Replace existing hvac unit with high efficiency model | $25,053 | $91,900 |
$19,992
283,173
kWh
|
$5,061
-
kW-mo/yr
|
- | |
04 | 2.7425: Clean or color roof to reduce solar load | $13,807 | $28,125 |
$10,702
151,589
kWh
|
$3,105
-
kW-mo/yr
|
- | |
05 | 2.4236: Eliminate leaks in inert gas and compressed air lines/ valves | $5,114 | $1,000 |
$3,681
52,137
kWh
|
$1,433
-
kW-mo/yr
|
- | |
06 | 2.7134: Use photocell controls | $1,975 | $5,550 |
$1,390
19,701
kWh
|
$585
-
kW-mo/yr
|
- | |
07 | 2.4133: Use most efficient type of electric motors | $1,832 | $4,400 |
$1,200
17,001
kWh
|
$632
-
kW-mo/yr
|
- | |
TOTAL RECOMMENDED | $196,589 | $161,200 |
$39,341
557,258
kWh
|
$158,139
-
kW-mo/yr
|
$(-891.0)
-
MMBtu
|
||
TOTAL IMPLEMENTED | $79,501 | $135,975 |
$36,965
523,601
kWh
|
$42,536
-
kW-mo/yr
|
- | ||
Yearly Savings* | Imp'd Cost* | Electricity Usage Savings | Electricity Demand Savings | Natural Gas Savings |
*Savings and costs are best estimates based on the center's site visit, associated engineering analysis, and typical capital and labor costs